Accumulator settings
13.12 Accumulator settings
Accumulator
has following menu items:
• ACC Temp Min On
• ACC Temp Min Off
• Discharge Pump On Temp
• Pump Depends on Require
• Pump type
• Pump Speed Controller
• Pump Switch Off Hyst
• Pump Run On Time
• Pump Control Range
For each heating circuit you can regulate one accumulator. You can operate a maximum of three heating
controllers in a system.
Therefore the number of accumulators is limited to 3. Connect the sensor of the accumulator to the heating
controller. Then perform
Periphery Learning
. In
Periphery Learning
you assign to the participants (heating
circuit or DHW) an accumulator.
Make further adjustments in the menu
Accumulator
.
If the temperature at the TPO (AC upper sensor) falls below the specified value of
ACC temp min
, a burner demand occurs to load the accumulator until the TPM (AC
middle sensor) reaches the limit.
The accumulator loads as long as the adjusted value of
Accumulator Temp Min Off
is reached.
If the temperature on the
accumulatorsensor rises
above the
Discharge Pump On
Temp
, all pumps allocated to the participants are set to active.
PE 567 EN 1.1
Содержание PE 08
Страница 16: ...16 Wiring diagrams PE 567 EN 1 1 ...
Страница 17: ...Wiring diagrams 17 Operating Manual PELLEMATIC PE S K B 10 56 ...
Страница 18: ...18 Wiring diagrams PE 567 EN 1 1 ...
Страница 76: ...76 Code Input Menu of Pelletronic Touch after entering the code PE 567 EN 1 1 ...
Страница 110: ...110 Cascade settings Back to the menu Sys Regulation PE 567 EN 1 1 ...
Страница 168: ......
Страница 169: ......