162
Malfunction report
Cause and Remedy:
Sensor defect
ڃ
Measure sensor (approx. 5 mV at 125°C) re-
place if required
Sensor cable defect
ڃ
Replace sensor
Sensor temperature too
low
ڃ
Sensor temperature below measuring range
(– 10°C)
Sensor polarity reversed
ڃ
Change sensor conn and –
Display:
[5048] PE Burner gas open-circuit
(only SMART without combustion cham-
ber sensor)
Description:
Burner gas sensor fracture, measuring circuit of Burner gas sensor is open –
Output RGF
Cause and Remedy:
Sensor not connected
ڃ
Connect sensor at input
Sensor cable defect
ڃ
Replace sensor
Sensor defect
ڃ
Measure sensor (NiCrNi) replace if required
Sensor temperature too
high
ڃ
Sensor temperature above measuring range
(1100°C)
Display:
[5049] PE Burner gas short-circuit
(only SMART without combustion cham-
ber sensor)
Description:
Burner gas sensor short circuit, measuring circuit of Burner gas sensor short
circuit – Output RGF
Cause and Remedy:
Sensor defect
ڃ
Measure sensor (approx.. 5mV at 125°C) re-
place if required
Sensor cable defect
ڃ
Replace sensor
Sensor temperature too
low
ڃ
Sensor temperature below measuring range
(– 10°C)
Sensor polarity reversed
ڃ
Change sensor conn and –
13.5 Underpressure box (Fault 5012, 5013, 5041, 5042)
Display:
[5012] PE Underpressure box BS
Description:
Negative draft input open, measuring circuit from negative draft measure-
ment open – Input UP
Cause and Remedy:
Signal incorrect
ڃ
Check poarity and signal (0-10V)
Signal cable defect
ڃ
Replace sensor
No signal
ڃ
Replace underpressure box
Combustion chamber leak
ڃ
Check total closure of boiler door
PE 567 EN 1.1
Содержание PE 08
Страница 16: ...16 Wiring diagrams PE 567 EN 1 1 ...
Страница 17: ...Wiring diagrams 17 Operating Manual PELLEMATIC PE S K B 10 56 ...
Страница 18: ...18 Wiring diagrams PE 567 EN 1 1 ...
Страница 76: ...76 Code Input Menu of Pelletronic Touch after entering the code PE 567 EN 1 1 ...
Страница 110: ...110 Cascade settings Back to the menu Sys Regulation PE 567 EN 1 1 ...
Страница 168: ......
Страница 169: ......