3-4. Programming Over Voltage Protection(OVP)
Overvoltage protection guards the load against output voltages that reach a specified value greater
than the programmed protection level. Below procedure is for setting the OVP level.
disable the OVP at the Factory Mode.
▌
Turn on the power supply
After turned on, check the power supply displays"**OUTPUT OFF**" Mode.
▌
Press the "Protection" key in other to enter the OVP menu
LCD Display
PROTECT> 1.OVP
▌
Press the "Protection" key one more time at the "1.OVP" state.
LCD Display
OVP SET> 32.00V
▌
Move the under bar cursor location where you want to change.
▌
Set the trip level.
Note that you cannot set the trip levels to lower than current real
output volt in order to prevent the operator's malfunction occurring.
▌
After set the trip levels that you want, press the "Protection" Key.
CHANGED
After displayed above message, The power supply will exit the OVP menu
and the display will return to the meter mode.
Cancelling
▌
If you don't want to change the OVP levels, just wait during 5 seconds.
Wait 5 sec
LCD Display
CANCEL…
≫ Related Remote Interface Command
VOLT:OVP {<voltage>}
VOLT:OVP?
VOLT:TRIP?
VOLT:CLE
Refer: VOLT:OVP 25
Set the OVP Level
VOLT:OVP?
Confirm the OVP Level
VOLT:OVP:TRIP?
Confirm tripped OVP
VOLT:OVP:CLE
Clear tripped OVP
About initial OVP setting, refer to Default Setting Values of "1-6. Check After Power On"
Note
- 30 -
LCD Display
Содержание EX 100-12
Страница 1: ...Programmable DC Power Supply User Manual www odacore com EX Series Manual Part NO 019EX 03...
Страница 4: ...Safety Symbol...
Страница 91: ...92...
Страница 92: ...93...