556 Chapter 17 Hardware procedures
241-1501-240 5.2S2
10 The timing cable shield needs to be grounded on one end. Normally, do
this on the site’s BITS shelf of the timing source generator.
11 Determine the signal strength of the timing signals for the alarm/BITS
module by connecting a line analyzer at the wire-wrap terminals on the
terminal block, then at the DB9 connector pins of the cable assembly. The
pins to test are identified in:
•
the table “Wiring pinout for J3 of cable assembly NTHW75”
(page 555)
•
the table “Wiring pinout for J4 of cable assembly NTHW75”
(page 555)
•
the figure “A timing cable assembly NTHW75” (page 557)
The range of DS1 signal strengths are identified in 241-1501-200
Passport 15000, 20000 Hardware Description. Depending on the length
of cable from the site source, you many need a thicker gauge cable to
provide adequate signal strength.
12 Connect the DB9 connector labelled J3 on the cable assembly to the J3
connection on the alarm/BITS module. Repeat for the J4 connection.
Содержание Passport 15000
Страница 1: ...Passport 15000 20000 Hardware Installation Maintenance and Upgrade 241 1501 240 ...
Страница 2: ......
Страница 4: ......
Страница 6: ...6 Publication history 241 1501 240 5 2S2 ...
Страница 32: ...32 Contents 241 1501 240 5 2S2 ...
Страница 48: ...48 About this document 241 1501 240 5 2S2 ...
Страница 52: ...52 Chapter 1 Overview of hardware tasks 241 1501 240 5 2S2 ...
Страница 70: ...70 Chapter 2 Safety considerations and best practices 241 1501 240 5 2S2 ...
Страница 84: ...84 Chapter 4 Alarm BITS module 241 1501 240 5 2S2 ...
Страница 94: ...94 Chapter 5 CP and FP cables 241 1501 240 5 2S2 ...
Страница 178: ...178 Chapter 11 Initial switch hardware installations 241 1501 240 5 2S2 ...
Страница 182: ...182 Chapter 12 MAC address module 241 1501 240 5 2S2 ...
Страница 216: ...216 Chapter 14 Power and ground hardware of a Passport 15000 or 20000 241 1501 240 5 2S2 ...
Страница 872: ...872 Chapter 17 Hardware procedures 241 1501 240 5 2S2 ...
Страница 873: ......