9 - 44
MELSEC-A
9 MAIN POSITIONING CONTROL
In circular interpolation control with center point designation, an angular velocity is
calculated on the assumption that operation is carried out at a command speed on
the arc using the radius calculated from the start point address and center point
address, and the radius is compensated in proportion to the angular velocity
deviated from that at the start point.
Thus, when there is a difference (error) between a radius calculated from the start
point address and center point address (start point radius) and a radius calculated
from the end point address and center point address (end point radius), the
composite speed differs from the command speed as follows.
Start point radius > End point radius: As compared with the speed without error,
the speed becomes slower as end point
address is reached.
Start point radius < End point radius: As compared with the speed without error,
the speed becomes faster as end point
address is reached.
Restrictions
(1) 2-axis circular interpolation control cannot be set in the following cases.
•
When "degree" is set in " Pr.1 Unit setting"
•
When the units set in " Pr.1 Unit setting" are different for the reference axis
and interpolation axis. ("mm" and "inch" combinations are possible.)
•
When "stepping motor mode" is set in " Pr.11 Stepping motor mode
selection"
•
When "reference axis speed" is set in " Pr.21 Interpolation speed
designation method"
(2) An error will occur and the positioning start will not be possible in the following
cases. The machine will immediately stop if the error is detected during
positioning control.
•
In case radius is over than "536870912(=2
29
)" which is the maximum and
acceptable radius for circular interpolation control, or in case the end address
is outside the scope of "-2147483648(-2
31
) to 2147483647(2
31
-1)".
... An error "end point setting error" (error code:526) or "outside radius
range" (error code: 544) will occur at positioning start.
•
When the start point address is the same as the center point address
... An error "center point setting error" (error code: 527) will occur.
•
When the end point address is the same as the center point address
... An error "center point setting error" (error code: 527) will occur.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание A1SD75P1-S3
Страница 2: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 16: ...A 13 MEMO Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 23: ...A 20 MEMO Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 25: ...MEMO Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 275: ...MEMO Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 617: ...Index 12 MEMO Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 620: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 621: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...