6 - 35
MELSEC-A
6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL
(5) Time chart for restarting
0
V
t
1
Dwell time
8
1
8
0
0
0
Positioning start signal
Axis stop signal
AD75 READY signal
Start complete signal
BUSY signal
Error detection signal
Cd.11 Positioning start No.
Positioning complete signal
PLC READY signal
Md.35 Axis operation status
[Y10]
[Y13]
[Y1D]
[X0]
[X1]
[X4]
[X7]
[XA]
Fig. 6.13 Time chart for restarting