Appendix - 51
MELSEC-A
APPENDICES
Trouble type
Questions/Trouble
Remedy
No.
Writing from the
computer link module
How can the address be
designated when writing data from
the computer link module to the
AD75?
Designate an address in the AD75 buffer memory
address "0" that will be interpreted as the computer link
module buffer memory address "800H".
(Refer to the User's Manual for the module being used for
details.)
54
Error 997 (speed selection at zero
point shift error) occurred. What
does "OPR" mean?
"OPR" stands for "Original Position Return", or in other
words, a zero point return.
55
Backlash compensation value
0
≤
Movement amount per pulse
≤
255
Error 938 (backlash compensation
amount error 2) occurs even when
the backlash compensation value
is set to "1".
Setting is not possible if the above equation is not
satisfied.
Adjust by setting "
Pr.4 Unit magnification" to 10-fold (or
100-fold, or 1000-fold), and setting " Pr.3 Movement
amount per rotation" to 1/10 (or 1/100, or 1/1000).
56
When a JOG operation is
attempted, errors such as error 104
(hardware stroke limit+) or error 105
(hardware stroke limit –) occur and
the machine does not move.
The hardware stroke limit wiring has probably not been
carried out.
Refer to section "12.4.4 Hardware stroke limit function" for
details, and wire accordingly.
57
Error 971 (tracking control mode
error) occurs. What could be
causing the error?
A value besides "0" or "1" may be set in the " Pr.44 Near
pass mode selection for path control".
Review the set sequence program, and reset the correct
parameters.
58
Error 997 (speed selection at zero
point shift error) appears when the
PLC READY signal [Y1D] turns
from OFF to ON.
A value besides "0" or "1" may be set in the " Pr.57
Speed designation during zero point shift".
Review the set sequence program, and reset the correct
parameters.
59
When the start signal was turned
ON immediately after the stop
signal ON, warning 100 (start
during operation) was detected,
and the start was ignored.
The AD75 starts the deceleration stop process when the
stop signal ON is detected. Thus, the machine interprets
that "positioning is still being executed" immediately after
the stop signal ON. Even if the start signal is turned ON at
that time, the start request will be ignored and warning
100 will occur.
60
Error/warning
Does warning 500 (deceleration
and stop speed change) occur
only during "stop deceleration" and
"automatically deceleration"?
Is there any problem if the
operation is continued in that state
without resetting the error?
The warning occurs only at those times mentioned at the
left. Because this is a warning, there is no problem if the
operation can be continued without resetting the error.
(When the speed is changed using the override, the new
value will not be reflected on the data being executed, but
will be reflected from the next start.)
61
Positioning may not have been completed normally due to
occurrence of a stop cause.
Check the axis monitor " Md.35 Axis operation status"
after the BUSY signal has turned OFF.
During stop: The stop signal has turned ON during
positioning. Check the condition under which
the stop signal (Y stop, external stop) turns
ON.
During error occurrence:
An error occurred during positioning. Confirm
the error occurrence cause from " Md.33
Axis error No.".
62
Positioning complete
signal
Position control was performed but
positioning complete signal does
not turn ON.
The setting of detailed parameter 2 "Positioning
completion signal output time" is 0 or shorter than the
scan time.
Set the time that can be detected securely in the
sequence program.
63
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание A1SD75P1-S3
Страница 2: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 16: ...A 13 MEMO Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 23: ...A 20 MEMO Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 25: ...MEMO Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 275: ...MEMO Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 617: ...Index 12 MEMO Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 620: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 621: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...