1. SPECIFICATIONS
INDOOR UNITS
1 - 38
PFFY
I.Floor standing (Concealed type)
1. SPECIFICATIONS
Model
PFFY-WP20VLRMM-E
PFFY-WP25VLRMM-E
PFFY-WP32VLRMM-E
PFFY-WP40VLRMM-E
Power source
1-phase 220-230-240 V 50/60
Hz
1-phase 220-230-240 V 50/60
Hz
1-phase 220-230-240 V 50/60
Hz
1-phase 220-230-240 V 50/60
Hz
Cooling capacity
*1 kW
2.2
2.8
3.6
4.5
(Nominal)
*1 kcal/h
1,900
2,400
3,100
3,900
*1 BTU/h
7,500
9,600
12,300
15,400
*2 Power input
kW
0.040
0.040
0.050
0.050
*2 Current input
A
0.35
0.35
0.47
0.47
Heating capacity
*3 kW
2.5
3.2
4.0
5.0
(Nominal)
*3 kcal/h
2,200
2,800
3,400
4,300
*3 BTU/h
8,500
10,900
13,600
17,100
*2 Power input
kW
0.040
0.040
0.050
0.050
*2 Current input
A
0.35
0.35
0.47
0.47
External finish
Galvanized steel plate
Galvanized steel plate
Galvanized steel plate
Galvanized steel plate
External dimension H x W x D
mm
639 x 886 x 220
639 x 1,006 x 220
639 x 1,006 x 220
639 x 1,246 x 220
in.
25-3/16 x 34-15/16 x 8-11/16
25-3/16 x 39-5/8 x 8-11/16
25-3/16 x 39-5/8 x 8-11/16
25-3/16 x 49-1/16 x 8-11/16
Net weight
kg (lbs)
22 (49)
25 (56)
25 (56)
29 (64)
Heat exchanger
Cross fin (Aluminum fin and
copper tube)
Cross fin (Aluminum fin and
copper tube)
Cross fin (Aluminum fin and
copper tube)
Cross fin (Aluminum fin and
copper tube)
Water Volume
L
0.9
1.3
1.3
1.5
FAN
Type x Quantity
Sirocco fan x 1
Sirocco fan x 2
Sirocco fan x 2
Sirocco fan x 2
*4 External static press.
Pa
20 - <40> - <60>
20 - <40> - <60>
20 - <40> - <60>
20 - <40> - <60>
mmH
2
O
2.0 - <4.1> - <6.1>
2.0 - <4.1> - <6.1>
2.0 - <4.1> - <6.1>
2.0 - <4.1> - <6.1>
Motor Type
DC motor
DC motor
DC motor
DC motor
Motor output
kW
0.096
0.096
0.096
0.096
Driving mechanism
Direct-driven by motor
Direct-driven by motor
Direct-driven by motor
Direct-driven by motor
Air flow rate
(Low-Mid-High)
(Low-Mid-High)
(Low-Mid-High)
(Low-Mid-High)
m
3
/min
4.5 - 5.0 - 6.0
6.0 - 7.0 - 8.0
7.5 - 9.0 - 10.5
8.0 - 10.0 - 11.5
L/s
75 - 83 - 100
100 - 117 - 133
125 - 150 - 175
133 - 167 - 192
cfm
159 - 177 - 212
212 - 247 - 282
265 - 318 - 371
282 - 353 - 406
Sound pressure level (measured in anechoic room)
(Low-Mid-High)
(Low-Mid-High)
(Low-Mid-High)
(Low-Mid-High)
*2 dB <A>
31-33-38
31-33-38
31-35-38
34-37-40
Insulation material
Polyethylene foam, Urethane
foam
Polyethylene foam, Urethane
foam
Polyethylene foam, Urethane
foam
Polyethylene foam, Urethane
foam
Air filter
PP honeycomb fabric.
PP honeycomb fabric.
PP honeycomb fabric.
PP honeycomb fabric.
Protection device
Fuse
Fuse
Fuse
Fuse
Refrigerant control device
-
-
-
-
Connectable outdoor unit
HYBRID CITY MULTI
/CMB-WP-V-G
HYBRID CITY MULTI
/CMB-WP-V-G
HYBRID CITY MULTI
/CMB-WP-V-G
HYBRID CITY MULTI
/CMB-WP-V-G
Water piping diameter
Inlet
in.
Rc 3/4 screw
Rc 3/4 screw
Rc 3/4 screw
Rc 3/4 screw
*5 *6 Outlet
in.
Rc 3/4 screw
Rc 3/4 screw
Rc 3/4 screw
Rc 3/4 screw
Field drain pipe size
mm (in.)
I.D.26 (1) <Accessory hose
O.D.27 (1-3/32) (top end:
O.D.20 (13/16))>
I.D.26 (1) <Accessory hose
O.D.27 (1-3/32) (top end:
O.D.20 (13/16))>
I.D.26 (1) <Accessory hose
O.D.27 (1-3/32) (top end:
O.D.20 (13/16))>
I.D.26 (1) <Accessory hose
O.D.27 (1-3/32) (top end:
O.D.20 (13/16))>
Drawing
External
KD94T792X01
KD94T792X01
KD94T792X01
KD94T792X01
Wiring
KD94T791X01
KD94T791X01
KD94T791X01
KD94T791X01
Refrigerant cycle
-
-
-
-
Standard attachment
Document
Installation Manual, Instruc-
tion Book
Installation Manual, Instruc-
tion Book
Installation Manual, Instruc-
tion Book
Installation Manual, Instruc-
tion Book
Accessory
Insulation pipe for water pipe,
Drain hose (flexible joint),
Screw plate, Level adjusting
screw, Hose band
Insulation pipe for water pipe,
Drain hose (flexible joint),
Screw plate, Level adjusting
screw, Hose band
Insulation pipe for water pipe,
Drain hose (flexible joint),
Screw plate, Level adjusting
screw, Hose band
Insulation pipe for water pipe,
Drain hose (flexible joint),
Screw plate, Level adjusting
screw, Hose band
Optional parts
Remarks
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred
to the Installation Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
Notes :
Unit converter
1.Nominal cooling conditions
Indoor: 27 °CD.B./19 °CW.B. (81 °FD.B./66 °FW.B.), Outdoor: 35 °CD.B. (95 °FD.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.The values are measured at the factory setting of external static pressure.
3.Nominal heating conditions
Indoor: 20 °CD.B. (68 °FD.B.), Outdoor: 7 °CD.B./6 °CW.B. (45 °FD.B./43 °FW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
4.The factory setting of external static pressure is shown without < >.
Refer to "Fan characteristics curves", according to the external static pressure, in DATA BOOK for the usable
range of air flow rate.
5.Be sure to install a valve on the water outlet.
6.Install a strainer (40 mesh or more) on the pipe next to the valve to remove the foreign matters.
7.Please group units that operate on 1 branch.
kcal
=kW x 860
BTU/h =kW x 3,412
cfm
=m
3
/min x 35.31
lbs
=kg/0.4536
*Above specification data is
subject to rounding variation.
Содержание PURY-WP-YJM-A
Страница 1: ...DATA BOOK PURY WP YJM A CMB WP V G PEFY WP VMS1 E PEFY WP VMA E PFFY WP VLRMM E MODEL 3rd edition ...
Страница 3: ...Databook ...
Страница 5: ...1 2 INDOOR UNITS ...
Страница 39: ...1 36 INDOOR UNITS ...
Страница 51: ...1 48 INDOOR UNITS ...
Страница 61: ...1 58 INDOOR UNITS ...
Страница 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Страница 69: ...2 2 OUTDOOR UNITS ...
Страница 85: ...2 18 OUTDOOR UNITS ...
Страница 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Страница 173: ...4 2 SYSTEM DESIGN ...