![Mitsubishi Electric PURY-WP-YJM-A Скачать руководство пользователя страница 155](http://html.mh-extra.com/html/mitsubishi-electric/pury-wp-yjm-a/pury-wp-yjm-a_data-book_1811269155.webp)
3. System remote controller
CONTROLLER
3 - 70
Contr
oller
(1-2) Output
Non-voltage Relay contact or transistor is available for output. Only one can be used at a time.
(a) Non-voltage Relay Contact Outputs
CAUTION
• To use X1 and Y1 relay, obtain one that satisfies the following specifications.
Operating coil
[Applied load]
MAX: 24 VDC, 5 W (Built-in diode)
MIN: 5 VDC, 2 mW (Built-in diode)
*1 AC loads cannot be connected.
*2 Provide a power supply (V1, V2) that matches the load and relay to be used.
• To drive a direct load, use ones within the following.
[Applied load]
MAX: 24 VDC, 5 W
MIN: 5 VDC, 2 mW
* AC loads cannot be connected.
• Make sure that the copper wiring is not short-circuiting the plates (cover, lower case) or neighboring wires.
• Perform wiring so that the terminal block is not strained.
If strained, use a wire guide or junction terminal to alleviate the stress on the terminal block.
• Do not connect the wires directly from the top of the control panel to the terminal block.
Moisture may enter this device along the wiring and cause electric shock or fire.
Operate (ON) output :
Contacts closed
Stop (OFF) output :
Contacts open
*Upon pulse output, the (ON), (OFF)
contacts close according to the output
content. ((ON) and (OFF) refer to the
junctions in the diagram.)
CN04
Ch1
Ch2
V2
Y1
Y1
X1
(OFF)
ON/OFF, (ON)
ON/OFF, (ON)
(OFF)
Load
Power supply
V1 (DC)
Power supply
V2 (DC)
Tightening torque for terminal screws: 1 N·m
Device
side
Field
Connections
( ) is in the case of a pulse.
Содержание PURY-WP-YJM-A
Страница 1: ...DATA BOOK PURY WP YJM A CMB WP V G PEFY WP VMS1 E PEFY WP VMA E PFFY WP VLRMM E MODEL 3rd edition ...
Страница 3: ...Databook ...
Страница 5: ...1 2 INDOOR UNITS ...
Страница 39: ...1 36 INDOOR UNITS ...
Страница 51: ...1 48 INDOOR UNITS ...
Страница 61: ...1 58 INDOOR UNITS ...
Страница 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Страница 69: ...2 2 OUTDOOR UNITS ...
Страница 85: ...2 18 OUTDOOR UNITS ...
Страница 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Страница 173: ...4 2 SYSTEM DESIGN ...