3. System remote controller
3 - 31
CONTROLLER
Controller
3-4. Centralized controller [GB-50ADA-J]
*GB-50ADA-J is indicated as GB-50ADA.
External dimension
Note: GB-50ADA can control up to 50 units. GB-50ADA is not connectable with PAC-YG50ECA.
License registration is necessary to perform each function on GB-50ADA.
Unit:mm[in.]
Item
Description
Operations Display
ON/OFF
Operation mode
switching
Fan speed setting
Air flow direction
setting
Ventilation
equipment
Temperature
setting
Run and stop operation for the air conditioner units
Switches between Cool / Dry / Auto / Fan / Heat.
(Group of LOSSNAY unit: automatic ventilation/ vent - heat interchange/ normal ventilation)
Operation modes vary depending on the air conditioner unit.
Air flow direction angles, 4-angle or 5-angle Swing, Auto
*1: Louver cannot be set.
*Air flow direction settings vary depending on the model.
The interlocked system settings can be performed by the master system controller.
When setting the interlocked system, you can use the ventilation switch to switch the free
plan LOSSNAY settings between "Hi", "Low" and "Stop".
When setting a group of only free plan LOSSNAY units, you can switch between "Normal
ventilation", "Interchange ventilation" and "Automatic ventilation".
Range of temperature setting
Cool/Dry : 19°C - 30°C (14°C - 30°C) / 67°F - 87°F(57°F - 87°F)
Heat : 17°C - 28°C (17°C - 28°C)/ 63°F - 83°F(63°F - 83°F)
Auto : 19°C - 28°C (17°C - 28°C)/ 67°F - 83°F(63°F - 83°F)
( ) in case of using middle-temperature on PEFY, PEFY-VML/VMR/VMS
/VMH-by setting DipSW7-1 to ON. Yet, PEFY-P-VMH-E-F is excluded.
* Range of temperature settings vary depending on model.
Sliding Temperature
setting
This function shifts the preset temperature by the preset increment to reduce the
temperature difference between the indoor and outdoor air temperatures during cooling
operation. The maximum shifting tempe1°C,+2°C,+3°C,+4°C) can be set for each group.
Schedule operation
Annual/Weekly (5 types)/today schedule can be set for each group of air conditioning units.
Optimized startup setting is also available.
*2: The system follows either the current day, annual schedule, or weekly, which are in
the descending order of overriding priority.
Twenty-four events can scheduled per day, including ON/OFF, Mode, Temperature
Setting, Operation Prohibition. Vane Direction, and Fan Speed.
Five types of weekly schedule(Summer/Winter) can be set.
Settable items depend on the functions that a given air conditioning unit supports.
Night setback setting
The function keeps the indoor temperature in a set temperature range once the unit stops
and during the time this function is effective.
Permit / Prohibit
local operation
Individually prohibit operation of each local remote control function (Start/Stop, Change
operation mode, Set temperature, Reset filter).
Indoor unit intake
temperature
Measures the intake temperature of the indoor unit only when the indoor unit is operating.
Interlock setting
Operation of indoor groups or general equipment can be interlocked by the change of state
(ON/OFF, mode, error of indoor groups and general equipment). (GB-50ADA will execute
interlocking control depending on the interlocked setting.)
Test run
This operates air conditioner units in test run mode.
Error
When an error is currently occurring on an air conditioner unit, the afflicted unit and the error
code are displayed.
When the local remote controller inactivation command is received from the master
system controller, "Disabled" appears in inverted display on the operation setting screen.
*3:
*1
The operation monitor screen shows the abnormal unit by flashing it. The error monitor
screen shows the abnormal unit address, error code and source of detection. The error
log monitor screen shows the time and date, the abnormal unit address, error code and
source of detection.
*4:
Models with 5 air flow speed settings: Hi/Mid-1/Mid-2/Low, Auto
Models with 4 air flow speed settings: Hi/Mid/Low, Auto
Models with 2 air flow speed settings: Hi/Low
*Fan speed settings vary depending on the model.
*2
*3
*4
*5
*5
:Each unit
:Collective
:Each block
:Each group
:Each floor
:Not available
Functions
External
input/output
M-NET
Collective
ON/OFF
The "M-NET" LED lights, when M-NET power supply is turned ON.
The LED blinks during M-NET communication.
All units can operate / stop with a DIP switch.
Data
back-up
(USB memory)
The initial setting data, operation data (charge parameter, power consumption data (*6)) can
be stored to a USB memory. Initial setting data can be read from USB memory.
By using accessory cables you can set the following.
Input: By level signal: "Batch start/stop", "Batch emergency stop"
By pulse signal: "Batch start/stop", "Enable/disable local remote controller"
*5: Requires the external I/O cable (PAC-YG10HA) sold separately and external power
supply.
By using accessory cables you can monitor the following.
Output: "Start/stop", "Error/Normal"
*5: Requires the external I/O cable (PAC-YG10HA) sold separately and external power
supply.
(LED)
(7 SEG)
*6: GB-50ADA Ver.2.45 or later
A.
*1
Microsoft
®
, Internet Explorer
®
is a registered trade mark of Microsoft
Corporation US in the USA and other countries.
Oracle
®
and Java
TM
are trademarks or registered trademarks of
Oracle corporation in the United States and/or other countries.
B. One GB-50ADA can control maximum 50 Indoor
units(including LOSSNAY). The integrated
centralized control software TG-2000A (*2) can
manage maximum 40 GB-50ADAs and maximum of
2000 units (including LOSSNAY).
C. GB-50ADA has a built-in function to supply power to
the M-NET transmission line. (power supply
coefficient: 6)
D. Taking advantage of GB-50ADA's Web functions,
alarming E-mail containing address and error code
can be sent to appointed E-mail address upon any
fault happen at the air conditioner system. This could
release standby personnel and save operation cost.
E. Together with integrated centralized control software
TG-2000A, and/or other controller (DIDO, AI,
PI controller), many optional functions like "Charging",
"Peak-cut", "Energy saving" etc, can be carried out.
F.
The interlock-control option enables interlocked operations of
air conditioning unit groups and the general equipment groups,
based on the changes of status in the ON/OFF, Mode, or Error
signals.
The central controller of GB-50ADA combines Web
function, which enable the air conditioner system
management on a PC browser screen. *1.
The management can even be carried out at a long
distance place via public telephone line or internet.
Microsoft
®
Internet Explorer
®
Ver. 6 or later by Microsoft Corporation is
recommended.
(As of December 2012, operation with Internet Explorer
®
Ver.6~9 are tested)
(Note: You must have operating system which complies with "Oracle
®
Java
TM
Plug-in". When using Internet Explorer
®
(64 bit), use Java
TM
Plug-in
(64bit).)
*2 TG-2000A Ver.6.30 or later is required to control GB-50ADA.
Connect GB-50ADA to a private network. Use a security
device such as a VPN router when connecting the
GB-50ADA to Internet to prevent unauthorized access.
Note:
97.2 (3-
7
/
8
)
250 (9-
7
/
8
)
155 (6-
1
/
8
)
204.5 (8-
1
/
16
)5
(
3
/
16
)
217 (8-
9
/
16
)
Error
M-NET
CN5
I/O
CN4
Serial
Serial number :
Ver. :
DB No. :
LINK/ACT LAN
MODEL :
Serial number :
Содержание PURY-WP-YJM-A
Страница 1: ...DATA BOOK PURY WP YJM A CMB WP V G PEFY WP VMS1 E PEFY WP VMA E PFFY WP VLRMM E MODEL 3rd edition ...
Страница 3: ...Databook ...
Страница 5: ...1 2 INDOOR UNITS ...
Страница 39: ...1 36 INDOOR UNITS ...
Страница 51: ...1 48 INDOOR UNITS ...
Страница 61: ...1 58 INDOOR UNITS ...
Страница 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Страница 69: ...2 2 OUTDOOR UNITS ...
Страница 85: ...2 18 OUTDOOR UNITS ...
Страница 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Страница 173: ...4 2 SYSTEM DESIGN ...