3. System remote controller
CONTROLLER
3 - 18
Contr
oller
(1). External signal input function
External signal input requires the external I/O adapter (Model: PAC-YT41HAA) sold separately.
1). External input
External no-voltage contact signal can be used to send signals indicating the following status of all air conditioning units that
are controlled : Emergency stop/Normal, ON/OFF, and local remote controller operation Prohibit/Permit.
The above settings can be made using the external input setting on the Initial Setting screen accessed from the
Service Menu screen.
No
1
2
3
4
External signal input function
Do not use external input signal
(factory setting)
Execute emergency stop/normal
with level signal
Perform ON/OFF with level signal
Perform ON/OFF, prohibit/enable
with pulse signals.
Remarks
The local remote controller ON/OFF operations, and the
controller ON/OFF operation and prohibit/enable change
operations will be prohibited during emergency stop.
The local remote controller ON/OFF operations, and the
controller ON/OFF operations and prohibit/enable change
operations will be prohibited.
Set the pulse width while the contact is ON to 0.2 to 1 sec.
3).
External input specifications
CN2
Lead wire
Emergency stop/normal level signal
ON/OFF, level signal
ON/OFF, prohibit/enable pulse signal
No.2
Yellow
Emergency stop/normal input
ON/OFF input
ON input
No.3
Orange
Not used
Not used
OFF input
No.4
Red
Not used
Not used
Local remote controller operation
prohibit input
No.5
Brown
Not used
Not used
Local remote controller operation
enable input
No.1
Green
Built-in power supply for external input (DC5V)
When the emergency stop/normal signal is selected, the status will change from normal to emergency stop when the
external input signal contact changes from OFF to ON, and will change from emergency stop to normal when the
contact changes from ON to OFF. Emergency stop signal will bring the air conditioners to stop, and canceling the
emergency stop will not automatically reset these units. To go back to the previous operation status, they must be
manually turned back on.
When the ON/OFF signal is selected, the status will change from OFF to ON when the external input signal contact
changes from OFF to ON, and will change from ON to OFF when the contact changes from ON to OFF.
(B) For pulse signal
Even if the ON signal is input during ON, the status will remain ON.
If the local remote controller is prohibited, the ON/OFF operation mode and temperature setting operations by the
local remote controller will be prohibited.
Set the pulse width (contact ON time) to 0.2 to 1 sec.
(A) For level signal
2).
Level signal and pulse signal
(A) Level signal
(B) Pulse signal
Contact ON
Contact OFF
OFF
OFF
ON
(Example) for ON/OFF
Contact ON
Contact OFF
0.2 to 1 sec
Contact ON
Contact OFF
Normal
Normal
Emergency stop
OFF
OFF
ON
Signal 1 (run)
Contact ON
Contact OFF
0.2 to 1 sec
Signal 2 (stop)
The prohibit/enable input is the same.
2. External input/output usage
External input connector
External output connector
Содержание PURY-WP-YJM-A
Страница 1: ...DATA BOOK PURY WP YJM A CMB WP V G PEFY WP VMS1 E PEFY WP VMA E PFFY WP VLRMM E MODEL 3rd edition ...
Страница 3: ...Databook ...
Страница 5: ...1 2 INDOOR UNITS ...
Страница 39: ...1 36 INDOOR UNITS ...
Страница 51: ...1 48 INDOOR UNITS ...
Страница 61: ...1 58 INDOOR UNITS ...
Страница 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Страница 69: ...2 2 OUTDOOR UNITS ...
Страница 85: ...2 18 OUTDOOR UNITS ...
Страница 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Страница 173: ...4 2 SYSTEM DESIGN ...