4. System component
CONTROLLER
3 - 84
Contr
oller
Indoor group can be controlled ON/OFF by an ON/OFF switching or contact input to
the connector of the head Indoor in an Indoor group.
It can be interlocked with timer, door, window, or other equipment to "Force stopping"
Indoor group can be controlled ON/OFF by an external pulse signal input to the
connector of the head Indoor in an Indoor group.
Indoor group can be controlled ON/OFF by an ON/OFF switching or contact input to
the connector of every Indoor in an Indoor group.
Signal output from a head Indoor unit, presenting its Indoor group.
It can be used for monitoring or interlock with other equipment purpose and so on.
Signal output from every Indoor unit, for monitoring Error or Thermo-off (fan) state.
It can be used for monitoring or interlock with other equipment purpose and so on.
Using connector
CN32
CN51
CN52
CN51
CN52
CN52
CN51
CN52
Signal
Input
(level-signal)
Input
(pulse-signal)
Input
(pulse-signal)
Output
Output
Table 4-1-3. Control can be achieved by using Indoor input/output connectors.
Remote/Local switching *1
ON/OFF *2*3
ON/OFF *2*3
Demand
Monitoring ON/OFF state
Monitoring heating state
Monitoring cooling/drying state
Monitoring Error state
Monitoring Thermo-OFF(fan) state
*1. When switching to Remote, control at Local remote controller will NOT be effective, but the "CENTRALLY CONTROLLED" is displayed.
*2. MA or ME remote controller is needed for this function.
*3. If using ON/OFF input function, Automatic-address-start-up can not be performed to start-up the system at commissioning.
*4. If HYBRID CITY MULTI use GB-50ADA/AG-150A and PLC software to control the Indoor unit via its external input/output connectors, Dip Switch 1-9 and Dip
Switch 1-10 should be set to ON.
In this case, the input/output connectors act as normal connectors, functions mentioned at Table 4-1-3. are no more available.
Details are available at the PLC software Instruction Manual.
All indoor units will turn ON and automatically resume to its previous mode after 5 minutes from
power recovery.
Indoor unit recovers to its previous state (ON/OFF, mode) after 5 minutes from power recovery.
Forced stopping regardless of Indoor units' state.
Setting Dip Switch *1*4
1-9
OFF
ON
OFF
1-10
ON
OFF
OFF
Auto ON
Auto recovery
All OFF
*1. The Dip Switch setting should be carried out on every Indoor unit in the group.
*2. Outdoor unit's power supply should NOT be cut. Otherwise, power supply to case heater of the compressor would be cut too, which may cause damage to the
compressor.
*3. Above method can not be applied to the power ON/OFF of the drain pump and humidifier equipment.
*4. If HYBRID CITY MULTI use GB-50ADA/AG-150A and PLC software to control the Indoor unit via its external input/output connectors, Dip Switch 1-9 and Dip
Switch 1-10 should be set to ON.
In this case, the input/output connectors act as normal connectors, functions mentioned at Table 4-1-4. are no more available.
Table 4-1-4. ON/OFF control to each Indoor unit (group) by using Dip Switch 9 and 10 (SW1-9, SW1-10) of the Indoor unit.
Usage
Function
Operation on Indoor units
Function
Table 4-1-6. Limitations to combining system controls
*1. Pulse ON/OFF, power ON/OFF and automatic recover can only be used when the remote/local setting CN32 is set to local.
Therefore, always avoid this function when combining control.
1
2
3
4
5
Control combining distant/local
Pulse ON/OFF
HA ON/OFF(JEMA)
Power ON/OFF
Automatic recover
CN32
CN51
CN51
-
-
-
Pulse ON/OFF
*1
-
Description
Power ON/OFF
*1
O
O
-
Automatic recover
*1
O
O
-
Control combining
distant/local
Outdoor unit
power supply
Outdoor unit
Indoor unit
HBC
controller
Local
remote
controller
Switch
Indoor unit
power supply
Restart of the HYBRID CITY MULTI needs to be careful. When no power supply to the outdoor unit, no power supply to the compressor case heater too.
The compressor needed to be warmed up before running. When using above functions, power supply to the outdoor unit should be ensured.
* For details refer to CN32 in section “4-3. Indoor unit “-E” type input/output connector”.
Operation is permitted
"CENTRALLY CONTROLLED" flashing, "ON/OFF" at local remote controller is not possible.
"CENTRALLY CONTROLLED" flashing, "ON/OFF" at local remote controller is not possible.
Local remote controller display and operation
State
CN32-SW-1
for Local/Remote
control switching
OFF
ON
ON
CN32-SW-2
for Remote
"ON/OFF" operation
OFF
OFF
ON
Table 4-1-5. How to use Remote/Local switching connector CN32
Local remote controller control
Remote STOP
Remote START
System example
Содержание PURY-WP-YJM-A
Страница 1: ...DATA BOOK PURY WP YJM A CMB WP V G PEFY WP VMS1 E PEFY WP VMA E PFFY WP VLRMM E MODEL 3rd edition ...
Страница 3: ...Databook ...
Страница 5: ...1 2 INDOOR UNITS ...
Страница 39: ...1 36 INDOOR UNITS ...
Страница 51: ...1 48 INDOOR UNITS ...
Страница 61: ...1 58 INDOOR UNITS ...
Страница 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Страница 69: ...2 2 OUTDOOR UNITS ...
Страница 85: ...2 18 OUTDOOR UNITS ...
Страница 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Страница 173: ...4 2 SYSTEM DESIGN ...