3. System remote controller
CONTROLLER
3 - 64
Contr
oller
3-14. DIDO controller [PAC-YG66DCA]
The DIDO controller is used in combination with a AG-150A/GB-50ADA to operate general-purpose equipment, as well as to monitor
operating and error status. It is equipped with two sets of standard terminals (Channels 1 and 2), and four sets of expansion connectors
for the input/output terminals. Expansion cable is optional.
Other devices can only be controlled from AG-150A/GB-50ADA Web browser and TG-2000A. Operation can be monitored or performed
from the AG-150A LCD.
In addition, this device includes a function that interlocks M-NET devices such as indoor units, general equipment, etc.
External Dimensions
CAUTION
Usage Restrictions
Unit: mm (in)
• Mitsubishi Electric does not take financial responsibility for damages caused by issues beyond our control or
special circumstances (predicable or unpredictable); and secondary or accidental damages, and damages to
other objects. We also do not take financial responsibility for opportunities lost as a result of device failure, or
electrical power failure at the end-user site.
Mitsubishi Electric does not take financial responsibility caused by end-users' requests including, but not
limited to, device testing, startup, readjustment, and replacement.
• Do not use this device in disaster prevention, security, or "critical to life" applications.
• It is recommended to provide an external switch for general-purpose equipment in case of a failure of the
DIDO controller or a peripheral part.
200 (7
7
/
8
)
111 (4
3
/
8
)
45 (1
25
/
32
)
107.6
( 4
1
/
4
)
15
(
19
/
32
)
11
0
(
4
11
/
32
)
26
( 1
1
/
32
)
120
( 4
3
/
4
)
26
( 1
1
/
32
)
150 (5
29
/
32
)
26 (1
1
/
32
)
83.5 (3
5
/
16
)
27 (1
3
/
32
)
52 (2
1
/
16
)
46.5 (1
27
/
32
)
4.5
(
3
/
16
)
[ 24 VDC Power Supply]
N623
DIDO
PAC-YG66DCA
MODEL
DIDO controller
SERVICE REF. PAC-
INPUT
WEIGHT
SERIAL No.
MADE IN JAPAN
YG66MCA-J
VOLTAGE
DC24V;0.2A
0.6 kg / 1 /
3 8 lb
PAC-YG66DCA
[ Output LEDs ]
ON/OFF
(ON)
(OFF) ON/OFF
(ON)
(OFF)
Ch2
Ch1
harmful interference, and (2)this device must accept any interference
received, including interference that may cause undesired operation.
subject to the following two conditions: (1)this device may not cause
This device complies with Part15 of the FCC Rules.Operation is
controller
[ INPUT ]
[ Expansion
ON/OFF
Error
Error
ON/OFF
Ch2
Ch1
I/O ]
Ch5,Ch6
Ch3,Ch4
[ OUTPUT ] Non-voltage Contact Output
ON/OFF,(ON)
ON/OFF,(ON)
(OFF)
(OFF)
ON/OFF,(ON)
(OFF)
ON/OFF,(ON)
[ Junction Terminal ]
[ OUTPUT ] Transistor Output
(OFF)
Ch2
Ch1
Ch2
Ch1
24 VDC
9
(
3
/
8
)
Содержание PURY-WP-YJM-A
Страница 1: ...DATA BOOK PURY WP YJM A CMB WP V G PEFY WP VMS1 E PEFY WP VMA E PFFY WP VLRMM E MODEL 3rd edition ...
Страница 3: ...Databook ...
Страница 5: ...1 2 INDOOR UNITS ...
Страница 39: ...1 36 INDOOR UNITS ...
Страница 51: ...1 48 INDOOR UNITS ...
Страница 61: ...1 58 INDOOR UNITS ...
Страница 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Страница 69: ...2 2 OUTDOOR UNITS ...
Страница 85: ...2 18 OUTDOOR UNITS ...
Страница 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Страница 173: ...4 2 SYSTEM DESIGN ...