![Mitsubishi Electric PURY-WP-YJM-A Скачать руководство пользователя страница 156](http://html.mh-extra.com/html/mitsubishi-electric/pury-wp-yjm-a/pury-wp-yjm-a_data-book_1811269156.webp)
3. System remote controller
3 - 71
CONTROLLER
Controller
(b) Transistor Outputs (Open Collector)
NOTE
The junction terminal block CN40 (for 24 VDC) is provided.
Use them as relay terminals if necessary.
CAUTION
• When X1, X2, Y1 and Y2 relays are used, select ones that satisfy the following specifications.
Operating coil
Rated voltage: 24 VDC (Built-in diode)
Power consumption: 0.9 W or less
(*1) Be sure to use the ones with the voltages rated above.
Exceeding the rated voltage may affect the ON/OFF of other outputs.
(*2) When using a separate power supply for this device, connect GND of the power supply to V- of CN16 of
the terminal block of this device.
(*3) Use a relay with a withstanding voltage of at least 2000 VAC between the coil and contact.
Otherwise, there is the likelihood of an electric shock or fire.
• Strip 12 1 mm (15/32 1/32 in) of the wire coating and insert firmly into the terminal.
• Make sure that the copper wiring is not short-circuiting the plates (cover, lower case) or neighboring wires.
• Perform wiring so that the terminal block is not strained.
If strained, use a wire guide or junction terminal to alleviate the stress on the terminal block.
• Do not connect the wires directly from the top of the control panel to the terminal block.
Moisture may enter this device along the wiring and cause electric shock or fire.
Operate (ON) output :
Transistor ON (sink)
Stop (OFF) output :
Transistor OFF (open)
*Upon pulse output, the
(ON),(OFF) transistors turn ON
(sink) according to the output
content. ((ON) and (OFF) refer
to the junctions in the diagram.)
/
/
/
X1
Y1
X2
Y2
Ch2
Ch1
FG
CN16
24 VDC Power source
V+/ V-/ FG
CN40
CN06
ON/OFF,
(ON)
ON/OFF,
(ON)
(OFF)
(OFF)
05
08
03
Field
Connections
24 VDC
Power
source
Device
side
Tightening torque for terminal screws: 1 N·m
( ) is in the case of a pulse.
Содержание PURY-WP-YJM-A
Страница 1: ...DATA BOOK PURY WP YJM A CMB WP V G PEFY WP VMS1 E PEFY WP VMA E PFFY WP VLRMM E MODEL 3rd edition ...
Страница 3: ...Databook ...
Страница 5: ...1 2 INDOOR UNITS ...
Страница 39: ...1 36 INDOOR UNITS ...
Страница 51: ...1 48 INDOOR UNITS ...
Страница 61: ...1 58 INDOOR UNITS ...
Страница 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Страница 69: ...2 2 OUTDOOR UNITS ...
Страница 85: ...2 18 OUTDOOR UNITS ...
Страница 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Страница 173: ...4 2 SYSTEM DESIGN ...