3. System remote controller
CONTROLLER
3 - 80
Contr
oller
2) Channel 1 (Channel 2) Analog Input (4 to 20 mADC, 1 to 5 VDC, 0 to 10 VDC)
CAUTION
• Select a power supply that is suitable for the sensor to be used.
• Do not install the sensor input line parallel to or near the M-NET transmission line or power line. Also avoid
loop wiring.
Furthermore, confirm the precautions for the sensor.
• Strip 12 1 mm (15/32 1/32 in) of the wire coating and insert firmly into the terminal.
• Make sure that the copper wiring is not short-circuiting the plates (cover, lower case) or neighboring wires.
• Perform wiring so that the terminal block is not strained.
If strained, use a wire guide or junction terminal to alleviate the stress on the terminal block.
(b) When 4 to 20 mADC
(type for which power is supplied to the signal line)
is connected
(a) When 1 to 5 VDC, 0 to 10 VDC, or 4 to 20 mADC
(type for which power is supplied to the sensor)
is connected
CN05
(CN08)
CN05
(CN08)
Sensor
Power supply
Field
Connections
Power supply
Sensor
Device side
Field
Connections
Device side
Содержание PURY-WP-YJM-A
Страница 1: ...DATA BOOK PURY WP YJM A CMB WP V G PEFY WP VMS1 E PEFY WP VMA E PFFY WP VLRMM E MODEL 3rd edition ...
Страница 3: ...Databook ...
Страница 5: ...1 2 INDOOR UNITS ...
Страница 39: ...1 36 INDOOR UNITS ...
Страница 51: ...1 48 INDOOR UNITS ...
Страница 61: ...1 58 INDOOR UNITS ...
Страница 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Страница 69: ...2 2 OUTDOOR UNITS ...
Страница 85: ...2 18 OUTDOOR UNITS ...
Страница 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Страница 173: ...4 2 SYSTEM DESIGN ...