2. Local remote controller
3 - 9
CONTROLLER
Controller
2-6. Wireless remote controller [PAR-FL32MA / PAR-FA32MA]
( ) For PEFY/PFFY by setting DipSW 7-1 to ON and limits to NI6H fan speed only.
Set to PAR-FL32MA according to its Installation Manual 4 "Model setting".
ON/OFF
ON and OFF operation for a single group
Operation mode
switching
Switches between Cool / Dry / Fan / Heat / Auto.
Operation modes vary depending on the air conditioner unit.
Temperature
setting
Sets the temperature for a single group
Range of temperature setting
Cool/Dry :
Heat :
Auto :
Fan speed setting
Models with 4 air flow speed settings: Hi/Mid-1/Mid-2/Low
Models with 3 air flow speed settings: Hi/Mid/Low
Models with 2 air flow speed settings: Hi/Low
Auto setting varies depending on the model.
Air flow direction
setting
Timer operation
One ON/OFF setting can be set for one day.
Permit / Prohibit
local operation
Individually prohibit operation of each local remote control
function (ON/OFF, Change operation mode, Set temperature,
Reset filter).
If operation is performed when the local remote controller
inactivation command is received from the main system
controller, a buzzer will ring and an LED will flash.
Indoor unit intake
temperature
Measures the intake temperature of the indoor unit when the
indoor unit is operating.
Error
When an error occurs on the air conditioner unit, the operation
lamp on the signal receiving unit will flash.
Test run
This operates air conditioner units in test run mode.
Ventilation
equipment
Up to 16 indoor units can be connected to an interlocked system
that has one LOSSNAY.
Item
Description
Operations Display
Air flow direction angles (4-angle, Swing) Auto Louver ON/OFF.
Air flow direction settings vary depending on the model.
1
Some models will have different display for the air flowdirection and fan speed.
Set the air flow direction and fan speed when performing initial setting.
:Each unit
:Collective
:Each block
:Each group
:Each floor
:Not available
It can operate in a group system without requiring
address settings.
When operating, it displays LED lamps. When
errors occur, the error code can be shown by the
LED flash count.
If an indoor unit with different functionality is operating inside the
same group, please note there may be cases when functionality
is partially disabled for batch control.
Wireless remote controllers can only be used for a single refrig-
erant system.
If you use a system controller to centrally control a group, you
will need cross-wiring between indoor units when using a wire-
less remote controller.
Also ensure there is no difference between the group setting of
the main system controller and the cross wiring across indoor
units when wiring and setting cross wires.
Signal
HBC controller
receiving
unit
Non-polarized
2-wire
Wireless
remote
controller
External dimension
ON/OFF
COOL
HEAT
9.9[
3
/
8
]
83.5[3-
9
/
32
]
19[
3
/
4
]
4.8[
3
/
16
]
35.2[1-
3
/
8
]
9.2[
3
/
8
]
4.6
[
3
/
16
]
22.5[
7
/
8
]
120[4-
23
/
32
]
70[2-
3
/
4
]
ON/OFF
COOL
HEAT
PAR-FL32MA
PAR-FA32MA
PAR-FL32MA
PAR-FA32MA
(Signal receiving unit)
System example
Functions
58[2-
9
/
32
]
159[6-
1
/
4
]
19[
3
/
4
]
ON/OFF
TEMP
MODEL SELECT
NOT AVAILABLE
CHECK TEST RUN
°C
AMPM
AMPM
Unit:mm[in.]
17°C - 28°C (17°C - 28°C) / 63°F - 83°F (63°F - 83°F)
19°C - 30°C (14°C - 30°C) / 67°F - 87°F (57°F - 87°F)
19°C - 28°C (17°C - 28°C) / 67°F - 83°F (63°F - 83°F)
Signal
receiving
unit
Non-
polarized
2-wire
Wireless
remote
controller
Non-
polarized
2-wire
Signal
receiving
unit
Wireless
remote
controller
Содержание PURY-WP-YJM-A
Страница 1: ...DATA BOOK PURY WP YJM A CMB WP V G PEFY WP VMS1 E PEFY WP VMA E PFFY WP VLRMM E MODEL 3rd edition ...
Страница 3: ...Databook ...
Страница 5: ...1 2 INDOOR UNITS ...
Страница 39: ...1 36 INDOOR UNITS ...
Страница 51: ...1 48 INDOOR UNITS ...
Страница 61: ...1 58 INDOOR UNITS ...
Страница 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Страница 69: ...2 2 OUTDOOR UNITS ...
Страница 85: ...2 18 OUTDOOR UNITS ...
Страница 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Страница 173: ...4 2 SYSTEM DESIGN ...