3 - 65
CONTROLLER
Controller
1. Specifications
(1). Device Specifications
*1: For details, refer to "1-(2). Parts Purchased Separately".
*2: Supply electric power from a power unit for the transmission line or an outdoor unit.
Furthermore, the power consumption factor of the M-NET circuitry of this device is "1/4" (equivalent to one ME Remote Controller).
*3: Non-voltage Relay contact or transistor is available for output. Only one can be used at a time.
*4: ( ) is in the case of a pulse.
*5: The output is open collector type. Power must be supplied from an external power source to the output circuit of this device.
*6: Power is supplied from this device to the external contacts.
*7: Power must be supplied from an external power source.
*8: M3 and M3.5 are sizes of the screw on the terminal block (ISO metric screw thread).
The number indicates the screw diameter (mm).
Item
Rating and Specification
Power Supply
24 VDC 10%: 5 W (*1)
Screw terminal block
(M3) (*8)
Interface
M-NET communication
17 to 30 VDC (*2)
Screw terminal block
(M3) (*8)
Output
(*3)
ON/OFF,
(ON)
(*4)
Non-voltage Relay contact (2)
Applied load
MAX: 24 VDC, 5 W
MIN: 5 VDC, 2 mW
* AC loads cannot be
connected.
Screw terminal block
(M3.5) (*8)
Transistor (2)
24 VDC 40 mA or less
(*5)
Screwless terminal
block
(OFF)
(*4)
Non-voltage Relay contact (2)
Applied load
MAX: 24 VDC, 5 W
MIN: 5 VDC, 2 mW
* AC loads cannot be
connected.
Screw terminal block
(M3.5) (*8)
Transistor (2)
24 VDC 40 mA or less
(*5)
Screwless terminal
block
Input
ON/OFF
Non-voltage a contact
(2 each)
24 VDC 1 mA or less
(*6)
Screwless terminal
block
Error/Normal
Output
ON/OFF, (ON)
(*4)
Transistor (4 each)
24 VDC 40 mA or less
(*5)
9 pin connector
(OFF) (*4)
Input
ON/OFF
24 VDC input (4 each)
24 VDC 1 mA or less
(*7)
9 pin connector
Error/Normal
Output Pulse Width
1s 30 ms
Interlock
Function
Interlock M-NET devices and output contacts according to status of input contacts. (*8)
Environment
Conditions
Temperature
Operating temperature range
0 to 40 [32 to 104 ]
Storage temperature range
-20 to 60 [-4 to 140 ]
Humidity
30 to 90%RH (no condensation)
Dimensions
200 (W) × 120 (H) × 45 (D) mm / 7
7
/
8
(W) × 4
3
/
4
(H) × 1
25
/
32
(D) in
Weight
0.6 kg / 1
3
/
8
lbs
Time Backup
During Power
Failure
In the event of power failure or shut-off, the internal capacitor will continue to track time for approximately one week.
(The internal capacitor takes about 24 hours to fully charge; a replacement battery is not necessary.)
Installation
Environment
Inside the metal control board (indoors)
* Use this product in a hotel, a business office environment or similar environment.
Standard
Expansion
1s 30 ms
Содержание PURY-WP-YJM-A
Страница 1: ...DATA BOOK PURY WP YJM A CMB WP V G PEFY WP VMS1 E PEFY WP VMA E PFFY WP VLRMM E MODEL 3rd edition ...
Страница 3: ...Databook ...
Страница 5: ...1 2 INDOOR UNITS ...
Страница 39: ...1 36 INDOOR UNITS ...
Страница 51: ...1 48 INDOOR UNITS ...
Страница 61: ...1 58 INDOOR UNITS ...
Страница 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Страница 69: ...2 2 OUTDOOR UNITS ...
Страница 85: ...2 18 OUTDOOR UNITS ...
Страница 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Страница 173: ...4 2 SYSTEM DESIGN ...