5. SOUND LEVELS
INDOOR UNITS
1 - 26
PEFY
-VMA
5. SOUND LEVELS
5-1. Sound levels
5-1-1. Sound levels (Measured condition : With 1m air inlet duct and 2m air outlet duct)
5-1-2. Sound levels (Measured condition : With 2m air inlet duct and 2m air outlet duct)
Sound level at anechoic room : Low-Mid-High
Model
Sound level dB(A)
35Pa
50Pa
70Pa
100Pa
150Pa
PEFY-WP20VMA-E
28-30-34
28-30-34
29-32-36
29-33-37
31-35-40
PEFY-WP25VMA-E
28-30-34
28-30-34
29-32-36
29-33-37
32-36-40
PEFY-WP32VMA-E
28-31-35
28-32-35
29-33-37
30-34-38
32-37-41
PEFY-WP40VMA-E
30-33-37
30-34-38
31-36-39
33-37-41
36-41-44
PEFY-WP50VMA-E
30-33-37
30-34-38
31-36-39
33-37-41
36-41-44
*
Measured in anechoic room.
PEFY-WP-VMA-E
2m
1m
Aux. duct
1.
5m
Measurement location
Sound level at anechoic room : Low-Mid-High
Model
Sound level dB(A)
35Pa
50Pa
70Pa
100Pa
150Pa
PEFY-WP20VMA-E
23-25-28
23-26-29
24-27-30
25-28-32
28-32-36
PEFY-WP25VMA-E
23-26-29
23-27-30
24-28-31
26-29-33
29-33-37
PEFY-WP32VMA-E
24-28-31
25-29-32
26-30-33
27-31-34
29-34-38
PEFY-WP40VMA-E
26-29-33
26-29-34
26-30-35
29-33-37
32-37-41
PEFY-WP50VMA-E
26-29-33
26-29-34
26-30-35
29-33-37
32-37-41
Measurement location
Aux. duct
*
Measured in anechoic room.
PEFY-WP-VMA-E
2m
2m
1.
5m
Содержание PURY-WP-YJM-A
Страница 1: ...DATA BOOK PURY WP YJM A CMB WP V G PEFY WP VMS1 E PEFY WP VMA E PFFY WP VLRMM E MODEL 3rd edition ...
Страница 3: ...Databook ...
Страница 5: ...1 2 INDOOR UNITS ...
Страница 39: ...1 36 INDOOR UNITS ...
Страница 51: ...1 48 INDOOR UNITS ...
Страница 61: ...1 58 INDOOR UNITS ...
Страница 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Страница 69: ...2 2 OUTDOOR UNITS ...
Страница 85: ...2 18 OUTDOOR UNITS ...
Страница 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Страница 173: ...4 2 SYSTEM DESIGN ...