![Mitsubishi Electric PURY-WP-YJM-A Скачать руководство пользователя страница 24](http://html.mh-extra.com/html/mitsubishi-electric/pury-wp-yjm-a/pury-wp-yjm-a_data-book_1811269024.webp)
1 - 21
1. SPECIFICATIONS
INDOOR UNITS
PEFY-VMA
Model
PEFY-WP50VMA-E
Power source
1-phase 220-230-240 V 50/
60 Hz
Cooling capacity
*1 kW
5.6
(Nominal)
*1 kcal/h
4,800
*1 BTU/h
19,100
*2 Power input
kW
0.14
*2 Current input
A
1.15
Heating capacity
*3 kW
6.3
(Nominal)
*3 kcal/h
5,400
*3 BTU/h
21,500
*2 Power input
kW
0.12
*2 Current input
A
1.04
External finish
Galvanized steel plate
External dimension HxWxD
mm
250 x 1,100 x 732
in.
9-7/8 x 43-5/16 x 28-7/8
Net weight
kg (lbs)
31 (69)
Heat exchanger
Cross fin (Aluminum fin and
copper tube)
Water Volume
L
1.8
FAN
Type x Quantity
Sirocco fan x 2
*4 External static press.
Pa
<35> - 50 - <70> - <100> -
<150>
mmH
2
O
<3.6> - 5.1 - <7.1> - <10.2> -
<15.3>
Motor Type
DC motor
Motor output
kW
0.121
Driving mechanism
Direct-driven by motor
Air flow rate
(Low-Mid-High)
m
3
/min
14.5 - 18.0 - 21.0
L/s
242 - 300 - 350
cfm
512 - 636 - 742
Sound pressure level (measured in anechoic room)
(Low-Mid-High)
*2 dB <A>
26-29-34
Insulation material
EPS, Polyethylene foam,
Urethane foam
Air filter
PP honeycomb fabric.
Protection device
Fuse
Refrigerant control device
-
Connectable outdoor unit/HBC controller
HYBRID CITY MULTI/CMB-
WP-V-G
Diameter of water pipe
Inlet
in.
Rc 3/4 screw
*5 *6 Outlet
in.
Rc 3/4 screw
Field drain pipe size
mm (in.)
O.D.32 (1-1/4)
Drawing
External
KD94L918X01
Wiring
KD94L919X01
Refrigerant cycle
-
Standard attachment
Document
Installation Manual, Instruc-
tion Book
Accessory
Insulation pipe for water pipe,
Washer, Drain hose, Tie
band
Optional parts
Filter box
PAC-KE93TB-E
Remarks
* Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.
* Due to continuing improvement, above specifications may be subject to change without notice.
Notes :
Unit converter
1.Nominal cooling conditions
Indoor: 27°CD.B./19°CW.B. (81°CD.B./66°CW.B.), Outdoor: 35°CD.B. (95°CD.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
2.The values are measured at the factory setting of external static pressure.
3.Nominal heating conditions
Indoor: 20°CD.B. (68°CD.B.), Outdoor: 7°CD.B./6°CW.B. (45°CD.B./43°CW.B.)
Pipe length: 7.5 m (24-9/16 ft.), Level difference: 0 m (0 ft.)
4.The factory setting of external static pressure is shown without < >.
Refer to "Fan characteristics curves", according to the external static pressure, in DATA BOOK for the usable
range of air flow rate.
5.Be sure to install a valve on the water outlet.
6.Install a strainer (40 mesh or more) on the pipe next to the valve to remove the foreign matters.
7.Group units that operate on 1 branch.
kcal
=kW x 860
BTU/h =kW x 3,412
cfm
=m
3
/min x 35.31
lbs
=kg / 0.4536
*Above specification data is
subject to rounding variation.
Содержание PURY-WP-YJM-A
Страница 1: ...DATA BOOK PURY WP YJM A CMB WP V G PEFY WP VMS1 E PEFY WP VMA E PFFY WP VLRMM E MODEL 3rd edition ...
Страница 3: ...Databook ...
Страница 5: ...1 2 INDOOR UNITS ...
Страница 39: ...1 36 INDOOR UNITS ...
Страница 51: ...1 48 INDOOR UNITS ...
Страница 61: ...1 58 INDOOR UNITS ...
Страница 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Страница 69: ...2 2 OUTDOOR UNITS ...
Страница 85: ...2 18 OUTDOOR UNITS ...
Страница 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Страница 173: ...4 2 SYSTEM DESIGN ...