3. System remote controller
3 - 55
CONTROLLER
Controller
<LMAP04-E Network Variables>
The proper communication is not obtainable when communication intervals exceed its performance, assure sufficient intervals.
ACK Service is recommended for the network service.
Detailed specifications for the L
ON
W
ORKS
network can be found in "FTT-10A Free Topology Transceiver User's Guide" or " FT3120/FT3150 Smart
Transceiver Data Book" by Echelon Corporation.
Please obtain the Network Variables Specification for details from your dealer.
Item
Description
TMPN3150/FT3150-P20 (10MHz)
Neuron CHIP
MITSUBISHI ELECTRIC
Connected Equipment
FTT-10A/FT-X1 (Free Topology 78kbps)
( For details of the connectable models,please contact the dealer.)
Network Transceiver
Performance
2.5 inputs/second
Average communication capacity
50 inputs/second (for one second)
Peak communication capacity
Multiple split-type air conditioners
Heat recovery ventilators
LM-AP can control 50 indoor units (including LOSSNAY)
Number of Units
HYBRID CITY MULTI
LOSSNAY
Environment specification
®
Indoor[1]-[50]
Network Variables
nv1n
nviOnOff_n
SNVT_switch
nv2n
nvoOnOff_n
SNVT_ switch
nv3n
nviMode_n
SNVT_hvac_mode
nv4n
nvoMode_n
SNVT_hvac_mode
nv5n
nviSetP_n
SNVT_temp_p
nv6n
nvoSetP_n
SNVT_temp_p
nv7n
nviCoolSetP_n
SNVT_temp_p
nv8n
nvoCoolSetP_n
SNVT_temp_p
nv9n
nviHeatSetP_n
SNVT_temp_p
nv10n
nvoHeatSetP_n
SNVT_temp_p
nv11n
nviAutoSetP_n
SNVT_temp_p
nv12n
nvoAutoSetP_n
SNVT_temp_p
nv19n
nviFanSpeed_n
SNVT_switch
nv20n
nvoFanSpeed_n
SNVT_switch
(*2, 3, 4)
(*9, 10, 11)
(*2, 3, 4)
(*2, 3, 4)
nv21n
nviProOnOff_n
SNVT_switch
nv22n
nvoProOnOff_n
SNVT_switch
nv23n
nviProMode_n
SNVT_switch
nv24n
nvoProMode_n
SNVT_switch
nv25n
nviProSetP_n
SNVT_switch
nv26n
nvoProSetP_n
SNVT_switch
(*2, 3, 4)
(*2, 3, 4)
(*2, 3, 4)
(*5)
(*8)
(*9)
(*9)
(*9, 10, 11)
(*8)
(*9)
(*9)
nv27n
nviThermoOff_n
SNVT_switch
nv28n
nvoThermoOff_n
SNVT_switch
(*5)
(*6)
nv29n
nviFiltReset_n
SNVT_switch
nv30n
nvoOnTime_n
SNVT_time_hour
(*6)
nv31n
nvoSpaceTemp_n
SNVT_temp_p
nv32n
nvoAlarm_n
SNVT_switch
nv33n
nvoErrCode_n
SNVT_count
nv34n
nvoErrAdrs_n
SNVT_count
nv35n
nvoThermoSt_n
SNVT_state
nv36n
nvoThermo_n
SNVT_switch
nv38n
nvoIcMdlSize_n
SNVT_count
nv39n
nvoGroupNo_n
SNVT_count
(*7)
Notes
*1: "n" of the network variable shows M-NET
address of indoor units.
*2: It may be unable to be used by the system
configuration of air-conditioners units.
*3: It is possible to use with an "MA or ME" remote controller.
*4: For the use of this function, turn ON the switch (SW1-1) on
LM ADAPTER. (Factory setting "OFF")
*5: For the use of this function, turn ON the switch (SW1-8) on
LM ADAPTER. (Factory setting "OFF")
*6: For the use of this function, turn ON the switch (SW1-4) on
LM ADAPTER. (Factory setting "OFF")
*7: It is possible to use with other system controller.
*8: This function is available only for the conventional indoor
units which don't support the dual setpoint.
*9: These functions are available for the units which support
the dual setpoint.
*10: This function is available for the DOAS was manufactured
in October, 2012 or later, when it uses for the DOAS.
*11: This function is available when the auto mode should be
controlled by single set point like the conventional one,
even when the dual set point is valid.
Содержание PURY-WP-YJM-A
Страница 1: ...DATA BOOK PURY WP YJM A CMB WP V G PEFY WP VMS1 E PEFY WP VMA E PFFY WP VLRMM E MODEL 3rd edition ...
Страница 3: ...Databook ...
Страница 5: ...1 2 INDOOR UNITS ...
Страница 39: ...1 36 INDOOR UNITS ...
Страница 51: ...1 48 INDOOR UNITS ...
Страница 61: ...1 58 INDOOR UNITS ...
Страница 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Страница 69: ...2 2 OUTDOOR UNITS ...
Страница 85: ...2 18 OUTDOOR UNITS ...
Страница 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Страница 173: ...4 2 SYSTEM DESIGN ...