3. System remote controller
CONTROLLER
3 - 50
Contr
oller
3-9. BACnet
®
interface [BAC-HD150]
HYBRID CITY MULTI can easily combine into a Building Management System (BMS) via the BACnet
®
and M-NET adapter
BAC-HD150. BACnet
®
is an opened transmission protocol widely used at BMS, and related equipment control.
HYBRID CITY MULTI is therefore compatible with large-scaled BMS management via BACnet
®
.
BAC-HD150 can control up to 50 units/groups (including LOSSNAY). Up to 150 units/groups(including LOSSNAY) can be
controlled from one BAC-HD150 with three expansion controllers PAC-YG50ECA. (50 units/PAC-YG50ECA)
When the dual set point function is used, no expansion controllers can be connected, and only up to 50 units/groups can be
controlled from each BAC-HD150.
Specifications
Items
Specifications
Rated input
100-240 VAC ±10 % 0.4-0.3 A 50/60 Hz
Power source
Fuse
250 VAC 3.15 A Time-delay type
(IEC127-2
S.S.5)
Rated output of the power supply
22-30 VDC
Interface
to M-NET transmission lines
LAN 1 (for BACnet)
10Base-T or 100Base-TX
LAN 2 (for Expansion Controller)
Operating
-10 ~ 55°C (14 ~ 131°F)
Ambient Temperature
temperature range
conditions
Storage
-20 ~ 60°C (-4 ~ 140°F)
temperature
range
Humidity
30 ~ 90 %RH (Non-condensing)
Dimensions
266 (H) × 250 (W) × 97.2 (D) mm
(10-
1
/
2
(H) × 9-
7
/
8
(W) × 3-
7
/
8
(D) in.)
Weight
2.8
kg
(6-
3
/
16
lbs.)
Installation conditions
Inside the metal control panel (indoor)
Operation
State Monitoring
Functions
Communication items at BM Adapter
External Dimensions
250(9-
7
/
8
)
155(6-
1
/
8
)
47.5(1-
7
/
8
)
97.2(3-
7
/
8
)
266(10-
1
/
2
)
253.5(10)
5(
3
/
16
)
M-NET Terminal block (M3.5)
LAN
Power source 100-240 VAC Terminal block (M3.5)
Terminal block
(to be used in the future
when functions of the
BAC-HD150 are upgraded.)
Unit:mm(in.)
On/Off
Mode
Fan Speed
Air Direction
Set Temp.
Set Temp. (Cool)*
Set Temp. (Heat)*
Set Temp. (Auto)*
Set Setback Temp. (Higher)*
Set Setback Temp. (Lower)*
Filter Sign reset
Prohibit local On/Off
Prohibit local Mode
Prohibit local Filter sign reset
Prohibit local Set Temp.
Forced Off
On/Off
Mode
Fan Speed
Air Direction
Set Temp.
Set Temp. (Cool)*
Set Temp. (Heat)*
Set Temp. (Auto)*
Set Setback Temp. (Higher)*
Set Setback Temp. (Lower)*
Filter sign
Indoor temperature
Prohibit local On/Off
Prohibit local Mode
Prohibit local Filter sign reset
Prohibit local Set Temp.
Alarm signal
Error code
Communication state
* When the dual set point
is used.
Содержание PURY-WP-YJM-A
Страница 1: ...DATA BOOK PURY WP YJM A CMB WP V G PEFY WP VMS1 E PEFY WP VMA E PFFY WP VLRMM E MODEL 3rd edition ...
Страница 3: ...Databook ...
Страница 5: ...1 2 INDOOR UNITS ...
Страница 39: ...1 36 INDOOR UNITS ...
Страница 51: ...1 48 INDOOR UNITS ...
Страница 61: ...1 58 INDOOR UNITS ...
Страница 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Страница 69: ...2 2 OUTDOOR UNITS ...
Страница 85: ...2 18 OUTDOOR UNITS ...
Страница 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Страница 173: ...4 2 SYSTEM DESIGN ...