3. System remote controller
3 - 75
CONTROLLER
Controller
1. Specifications
(1). Device Specifications
*1: Supply electric power from a power supply unit for the transmission line or an outdoor unit. Furthermore, the power consumption
factor of the MNET circuitry of this unit is "1/4" (equivalent to one ME Remote Controller).
*2: Configure the dip switch settings for the analog input method to use.
*3: The measurement error for the system includes the measurement error for this unit, sensor, and wiring.
a%FS (full scale) = a% × ([measurement range's upper limit value] - [lower limit value])
*4: Settings for the interlock function are performed from the Maintenance Tool. For details, refer to the operation manual for the
Maintenance Tool.
*5: M3 and M3.5 are sizes of the screw on the terminal block (ISO metric screw thread). The number indicates the screw diameter
(mm).
Item
Description
Power
Supply
24 VDC 10%: 5 W
Screw terminal
block (M3) (*5)
Interface
M-NET communication
17 to 30 VDC (*1)
Screw terminal
block (M3) (*5)
Input
Ch
Sensor
Measurement
target
Measurement
range
Measurement error
External
connection method
Ch1
Pt100
(3-wire system)
Temperature
-30 to 60
[-22 to 140 ]
0.3%FS 0.1 (0.18 )
(*3)
[at 25 (77 )]
Screwless terminal
block (3 poles)
Analog
4 to 20 mADC
Temperature/
humidity
(Set by system
controller)
0.5%FS 0.1 (0.18 )
(*3)
0.5%FS 0.1%RH
[at 25 (77 )]
Screwless terminal
block (2 poles)
1 to 5 VDC
0 to 10 VDC
Ch2
Analog
4 to 20 mADC
Temperature/
humidity
(Set by system
controller)
0.5%FS 0.1 (0.18 )
(*3)
0.5%FS 0.1%RH
[at 25 (77 )]
Screwless terminal
block (2 poles)
1 to 5 VDC
(*2)
0 to 10 VDC
Output
Upper/lower limit
alarm interlock output
(non-voltage contact)
Applied load
MAX: 24 VDC, 5 W
MIN: 5 VDC, 2 mW
* AC loads cannot be connected.
Screw terminal
block (M3.5) (*5)
Interlock
Function
Interlock M-NET devices according to measurement data values. (*4)
Environment
Conditions
Temperature
Operating temperature range
0 to 40 [32 to 104 ]
Storage temperature range
-20 to 60 [-4 to 140 ]
Humidity
30 to 90%RH (no condensation)
Dimensions
200 (W) × 120 (H) × 45 (D) mm / 7
7
/
8
(W) × 4
3
/
4
(H) × 1
25
/
32
(D) in
Weight
0.6 kg / 1
3
/
8
lb
Time Backup
During Power
Failure
In the event of power failure or shut-off, the internal capacitor will continue to track time for approximately one week.
(The internal capacitor takes about 24 hours to fully charge; a replacement battery is not necessary.)
Installation
Environment
Inside the metal control board (indoors)
* Use this product in a hotel, a business office environment or similar environment.
Содержание PURY-WP-YJM-A
Страница 1: ...DATA BOOK PURY WP YJM A CMB WP V G PEFY WP VMS1 E PEFY WP VMA E PFFY WP VLRMM E MODEL 3rd edition ...
Страница 3: ...Databook ...
Страница 5: ...1 2 INDOOR UNITS ...
Страница 39: ...1 36 INDOOR UNITS ...
Страница 51: ...1 48 INDOOR UNITS ...
Страница 61: ...1 58 INDOOR UNITS ...
Страница 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Страница 69: ...2 2 OUTDOOR UNITS ...
Страница 85: ...2 18 OUTDOOR UNITS ...
Страница 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Страница 173: ...4 2 SYSTEM DESIGN ...