2. EXTERNAL DIMENSIONS
OUTDOOR UNITS
2 - 6
OUTDOOR
Secure enough space around the unit as shown in the figure below
.
In case of single installation
1.Required space around the unit
2.Foundation work
When the height of the walls on the front,back or on the sides<H>
exceeds the wall height limit as defined below
add the height that exceeds the height limit <h> to the figures that
are marked with an asterisk.
<W
all height limit> Front :Up to the unit height
Back :Up to 500mm from
the unit bottom
Side :Up to the unit height
<T
op view>
<T
op view>
Front
Front
<T o be left open>
Front
H
h
h
H
Unit height
30 min.
450 min.
450 min.
15 min.*
15 min.*
50 min.*
50 min.*
300 min.*
450 min.*
100 min.*
450 min.*
300 min.*
450 min.*
15 min.*
500
<T o be left open>
<T o be left open>
<T o be left open>
<T o be left open>
<T o be left open>
<T o be left open>
<Side view>
100 min.*
450 min.*
100 min.
450 min.*
450 min.
450 min.
100 min.*
300 min.*
900 min.
300 min.*
300 min.*
900 min.
1000 min.*
Detachable leg
30mm max.
M10 anchor bolt
<field supply required>
Corner of the
installation leg
Corner of the
installation leg
M10 anchor bolt <field supply required>
30mm max.
· With a space of at least
100mm to the wall on
the back of the unit
· With a space of at least
300mm to the wall on
the back of the unit
<field supply required>
<field supply required>
Detachable leg
<Unit:mm>
W
all <H>
W
all <H>
Front
W
all <H>
Front
Front
Front
W
all <H>
W
all <H>
Front
Front
Front
Front
<T
o be left open>
<T
o be left open>
Wall<H>
Wall <H>
W
all<H>
Front
<T
o be left open>
<Unit:mm>
W
all <H>
W
all <H>
Front
When multiple units are installed adjacent to each other
, secure enough space to allow
for air circulation and walkway between groups of units as shown in the figures below
.
At least two sides must be left open.
As with the single installation, add the height that exceeds the height limit <h>
to the figures that are marked with an asterisk.
If there is a wall at both the front and the rear of the unit, install up to six units
consecutively in the side direction and provide a space of 1000mm or more as inlet space/
passage space for each six units.
In case of collective installation
Take into consideration the surface strength,water drainage route,
piping route,and wiring route when preparing the installation site.
<Note that the drain water comes out of the unit during operation.>
Build the foundation in such way that the corner of the installation leg is
securely supported as shown in the right figure.(Fig.A,B)
When using a rubber isolating cushion, please ensure it is large enough
to cover the entire width of each of the unit's legs.
The protrusion length of the anchor bolt must not exceed 30mm.(Fig.A,B)
Use four fixing plates as shown in the right figure <field supply required>
when using post-installed anchor bolts.(Fig.C,D)
To prevent small animals and water and snow from entering the unit and damaging
its parts,close the gap around the edges of through holes for pipes and wires
with filler plates <field supply required>.
When the pipes or cables are routed at the bottom of the unit,
make sure that the through hole at the base of the unit does not get blocked
with the installation base.
Refer to the Installation Manual when installing units on an installation base.
Fig.A
(without detachable legs)
Fig.B (with detachable legs)
Fixing plate
Fig.C (without detachable legs)
Fig.D (with detachable legs)
Fixing plate
1
2
1
2
4
3
5
6
7
1
2
4
3
PURY-WP200,250YJM-A
Unit : mm
Содержание PURY-WP-YJM-A
Страница 1: ...DATA BOOK PURY WP YJM A CMB WP V G PEFY WP VMS1 E PEFY WP VMA E PFFY WP VLRMM E MODEL 3rd edition ...
Страница 3: ...Databook ...
Страница 5: ...1 2 INDOOR UNITS ...
Страница 39: ...1 36 INDOOR UNITS ...
Страница 51: ...1 48 INDOOR UNITS ...
Страница 61: ...1 58 INDOOR UNITS ...
Страница 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Страница 69: ...2 2 OUTDOOR UNITS ...
Страница 85: ...2 18 OUTDOOR UNITS ...
Страница 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Страница 173: ...4 2 SYSTEM DESIGN ...