6. CAPACITY TABLES
2 - 13
OUTDOOR UNITS
OUT
DOOR
6-3. Correction by piping length
A decrease in cooling/heating capacity will occur due to piping length increase. Using the following correction factors according to
the equivalent length of the piping shown at 6-3-1 and 6-3-2 the capacity can be calculated. 6-3-3 shows how to obtain the equiv-
alent length of piping. Refrigerant piping and water piping have separate correction factors.
6-3-1. Cooling capacity correction
PURY-WP200YJM-A
Total capacity of indoor unit
100
150
200
300
HBC to outdoor unit refrigerant piping equivalent length (m)
Cooling capacity correction factor
1
0.90
0.80
0.95
0.85
0.75
0.65
0.70
0
20
40
60
80
100
120
PURY-WP200YJM-A
Water piping equivalent length to farthest indoor unit (m)
Cooling capacity correction factor
1
0.98
0.96
0.99
0.97
0.95
0.93
0.94
0
10
20
30
40
50
60
70
PURY-WP250YJM-A
Total capacity of indoor unit
125
188
250
375
HBC to outdoor unit refrigerant piping equivalent length (m)
Cooling capacity correction factor
1
0.90
0.80
0.95
0.85
0.75
0.65
0.70
0
20
40
60
80
100
120
PURY-WP250YJM-A
Water piping equivalent length to farthest indoor unit (m)
Cooling capacity correction factor
1
0.98
0.96
0.99
0.97
0.95
0.93
0.94
0
10
20
30
40
50
60
70
Содержание PURY-WP-YJM-A
Страница 1: ...DATA BOOK PURY WP YJM A CMB WP V G PEFY WP VMS1 E PEFY WP VMA E PFFY WP VLRMM E MODEL 3rd edition ...
Страница 3: ...Databook ...
Страница 5: ...1 2 INDOOR UNITS ...
Страница 39: ...1 36 INDOOR UNITS ...
Страница 51: ...1 48 INDOOR UNITS ...
Страница 61: ...1 58 INDOOR UNITS ...
Страница 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Страница 69: ...2 2 OUTDOOR UNITS ...
Страница 85: ...2 18 OUTDOOR UNITS ...
Страница 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Страница 173: ...4 2 SYSTEM DESIGN ...