2. M-NET control
4 - 9
SYSTEM DESIGN
Sy
stem
2-2. Transmission cable specifications
Type of cable
Cable size
Remarks
Sheathed 2-core cable (unshielded)
CVV
2
Shielding wire (2-core)
CVVS, CPEVS or MVVS
Transmission cables
ME Remote controller cables
CVVS, MVVS : PVC insulated PVC jacketed shielded control cable
CPEVS :
*1 Connected with simple remote controller.
*2 To wire PAR-31MAA, simple MA remote controller use a wire with
a diameter of 0.3 mm
2
[AWG22]
*3 When a PAR-31MAA is connected to a group, no other MA remote
controllers can be connected to the same group.
PE insulated PVC jacketed shielded communication cable
CVV : PV insulated PVC sheathed control cable
—
Max length : 200m [656ft]
(L
i
)
MA Remote controller cables
When 10m [32ft] is exceeded, use cables with
the same specification as transmission cables.
More than 1.25 [AWG16]
2
0.3 1.25 [AWG22 16]
(0.75 1.25 [AWG18 16])
2
2
0.3 1.25 [AWG22 16]
(0.75 1.25 [AWG18 16])
Содержание PURY-WP-YJM-A