APPX
Appendix 4 List of Link Special Relay (SB)
269
A
SB0036
RECV execution
request flag CH7
Stores the data reception status of own station channel 7.
Off: No data received
On: Data received
SB0037
RECV execution
request flag CH8
Stores the data reception status of own station channel 8.
Off: No data received
On: Data received
SB0040
Network type of own
station
Stores the network type of the own station.
On: CC-Link IE TSN
SB0043
Module operation
mode of own station
Stores the module operation mode of the own station.
Off: Online mode
On: Other than online mode
SB0044
Station setting 1 of
own station
Stores the station type of the own station.
Off: Slave station (other than the master station)
On: Master station
SB0045
Station setting 2 of
own station
Stores the communication mode of the own station.
Off: Unicast mode
On: Multicast mode
SB0046
Station number setting
status of own station
Stores the station number setting status.
Off: Station number set
On: Station number not set (local station only)
If parameters are set using the engineering tool, this relay is always off.
SB0049
Data link error status of
own station
Stores the data link error status of the own station.
Off: Normal
On: Error
When this relay is turned on, the cause of the error can be checked with
'Cause of data link stop' (SW0049). Depending on the link refresh timing, the
update of 'Cause of data link stop' (SW0049) may be offset by one sequence
scan.
(Also used in the CLPA conformance test.)
(Updated even if set as an error invalid station.)
SB004A
CPU minor error status
of own station
Stores the minor error status of the CPU module on the own station.
Off: No minor error
On: Minor error
SB004B
CPU moderate/major
error status of own
station
Stores the moderate/major error status of the CPU module on the own
station.
Off: No moderate/major error
On: Moderate/major error
SB004C
CPU operating status
of own station
Stores the operating status of the CPU module on the own station.
Off: RUN, PAUSE
On: STOP or moderate/major error
SB004D
Received parameter
error
Stores the status of received parameter. (For the master station, this relay
stores the parameter status of the own station)
Off: Normal
On: Error
SB004F
Station number status
of the operating station
Stores the station number setting method as follows when the station type of
the own station is local station.
Off: Set by parameters
On: Set by program
Stores the station number setting method as follows for a remote device
station or intelligent device station.
Off: Set by parameters
On: Set by the CC-Link IE Field Network diagnostics (including cases with
no parameter and when the parameter is default (empty))
No.
Name
Description
Availability
Master
station
Local station
Unicast
mode
Multicast
mode
Содержание MELSEC iQ-R CC-Link IE TSN