4 TROUBLESHOOTING
4.5 List of Error Codes
231
4
DA00H
An error was detected in the network
module.
Please consult your local Mitsubishi representative.
DA10H
to
DA17H
An error was detected in the network
module.
Please consult your local Mitsubishi representative.
DA19H
An error was detected in the network
module.
Please consult your local Mitsubishi representative.
DA1AH
After parameters were set using the
CCPASETX instruction/CCPASET
instruction, the CCPASETX instruction/
CCPASET instruction were executed again.
Parameter setting with the CCPASETX instruction is limited to one time only.
Execute the instruction again after resetting the CPU module.
DA1BH
A dedicated instruction which the target
station does not support was executed.
• Change the target station at the station that executed the READ/SREAD/
WRITE/SWRITE/SEND/REQ instruction.
• Correct the network number and station number/IP address of the target
station of the dedicated instruction.
DA1CH
The target station of the READ/SREAD/
WRITE/SWRITE/SEND/REQ instruction
does not exist.
If the target station of the READ/SREAD/WRITE/SWRITE/SEND/REQ
instruction is disconnected, execute the dedicated instruction again after
return of the target station.
DB00H
The station numbers of 121 stations or more
are specified.
Check station numbers.
DC00H
The setting value is incorrect.
Execute the write instruction again after correcting the setting value.
DC01H
The setting value was not written correctly.
Execute the write instruction again. Please consult your local Mitsubishi
representative.
Error
code
Error definition and causes
Action
Detailed
information 1
Detailed
information 2
Содержание MELSEC iQ-R CC-Link IE TSN
Страница 1: ...MELSEC iQ R CC Link IE TSN User s Manual Application RJ71GN11 T2 ...
Страница 2: ......
Страница 160: ...158 3 PROGRAMMING 3 3 Communication Example of Safety Communication Master station station No 0 ...
Страница 323: ...APPX Appendix 10 Added and Enhanced Functions 321 A MEMO ...
Страница 325: ...I 323 MEMO ...
Страница 329: ......