4 TROUBLESHOOTING
4.5 List of Error Codes
229
4
D653H
Parameter error (transient transmission
group setting)
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the transient transmission
group setting in the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D654H
Parameter error (dynamic routing setting)
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting the dynamic routing setting
in the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D655H
Network addresses of the master station and
slave stations are incorrect.
Correct the IP address setting of the master station or slave stations.
D656H
Parameter error (CANopen communications)
Update the version of the engineering tool that supports the CANopen
communication function, then write parameters to the CPU module again.
D657H
Parameter error (station sub-ID)
• Write the network parameter to the CPU module again.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D658H
Parameter error (multidrop number)
• Write the network parameter to the CPU module again.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D659H
Parameter error (CANopen communication)
The CANopen communication function cannot be used. Clear the PDO
mapping setting in the engineering tool, and write the parameter to the CPU
module again.
D65AH
Parameter error (maximum number of
connectable stations)
• Parameters are set over the maximum number of connectable stations.
Correct the parameter so that the number of slave stations is 120 or less,
then write parameters to the CPU module again. Note that a PDO-
mapped extension module (for example, a multi-axis servo amplifier) to
which a station number is not set is counted as one station.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D65BH
Parameter error (CC-Link IE TSN Class
setting)
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting "CC-Link IE TSN Class
Setting" in the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D65CH
Parameter error (TSN hub setting)
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting "TSN HUB Setting" in the
setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D65DH
Parameter error (multiple period setting)
• Write the network parameter to the CPU module again.
• Execute the instruction again after correcting "Multiple Period Setting" in
the setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D840H
Number of transient requests exceeded the
upper limit of simultaneously processable
requests.
• Execute the instruction again after pausing the transient transmission
temporarily.
• Execute the instruction again after lower the transient transmission usage
frequency.
D841H
The request data size of memory read/write
command is out of range.
Execute the instruction again after correcting the read or write size
specification at the transient request source.
D842H
• Routing information to the destination
network number is not registered.
• In transient transmission, the number of
relays to other networks exceeded seven.
• The communication path is being updated.
• Execute the instruction again after correcting the target network number
at the transient request source.
• Execute the instruction again after correcting the communication path
from the transient request source to the destination.
• When the dynamic routing is not used, or the module of the series other
than MELSEC iQ-R is included, retry the operation after correcting the
routing setting.
• Change the system configuration so that the number of relay stations is
seven or less.
• Transient transmission cannot be performed while the communication
path is being updated. Retry the operation.
Error
code
Error definition and causes
Action
Detailed
information 1
Detailed
information 2
Содержание MELSEC iQ-R CC-Link IE TSN
Страница 1: ...MELSEC iQ R CC Link IE TSN User s Manual Application RJ71GN11 T2 ...
Страница 2: ......
Страница 160: ...158 3 PROGRAMMING 3 3 Communication Example of Safety Communication Master station station No 0 ...
Страница 323: ...APPX Appendix 10 Added and Enhanced Functions 321 A MEMO ...
Страница 325: ...I 323 MEMO ...
Страница 329: ......