104
2 PARAMETER SETTINGS
2.3 Basic Settings
Connection Device Information
Set the information of the connected device.
Precautions
• For a structure with mixed CC-Link IE TSN Class B devices and CC-Link IE TSN Class A devices, set "TSN HUB Setting"
to "Use TSN HUB" when connecting a TSN hub.
• When "Network Topology" is set to "Ring", set "CC-Link IE TSN Class Setting" of "Connection Device Information" to "CC-
Link IE TSN Class B Only". If "Mixture of CC-Link IE TSN Class B/A or CC-Link IE TSN Class A Only" is set, an error code
(3016H) is output.
• When "TSN HUB Setting" is set to "Not to Use TSN HUB" and a TSN hub is connected, the slave station may not perform
data link. (
Page 201 CC-Link IE TSN Class A device does not perform data link)
Slave Station Setting
Set items related to the slave station.
Safety Communication Setting
Set whether to use the safety communication or not and set safety connections.
Set the following items before configuring the safety communication setting.
• "Network Configuration Settings" in "Basic Settings" (
Page 117 "CC-Link IE TSN Configuration"
If the above items are not set, the slave station is not displayed as the target module in the "Select the target
module for the Safety Communication Setting" window and safety communications cannot be set.
Item
Description
Setting range
CC-Link IE TSN
Class Settings
Set the CC-Link IE TSN Class of the connected device.
• CC-Link IE TSN Class B Only
• Mixture of CC-Link IE TSN Class B/A or
CC-Link IE TSN Class A Only
(Default: CC-Link IE TSN Class B Only)
TSN HUB Setting
Set whether to use a TSN hub or not when using a structure of mixed CC-Link IE TSN
Class B devices and CC-Link IE TSN Class A devices.
Set "Use TSN HUB" when connecting a TSN hub.
• Not to Use TSN HUB
• Use TSN HUB
(Default: Not to Use TSN HUB)
Item
Description
Setting range
Disconnection
Detection
Setting
Set the number of consecutive communication failures until a slave station is considered disconnected.
• 2 times
• 4 times
• 8 times
(Default: 4 times)
Item
Description
Setting range
To Use or Not to Use the Safety
Communication Setting
Set whether to use the safety communication or not.
• Not Use
• Use
(Default: Not Use)
Safety Communication Setting
Set the safety connections and transfer ranges of safety devices required for safety
communications.
Содержание MELSEC iQ-R CC-Link IE TSN
Страница 1: ...MELSEC iQ R CC Link IE TSN User s Manual Application RJ71GN11 T2 ...
Страница 2: ......
Страница 160: ...158 3 PROGRAMMING 3 3 Communication Example of Safety Communication Master station station No 0 ...
Страница 323: ...APPX Appendix 10 Added and Enhanced Functions 321 A MEMO ...
Страница 325: ...I 323 MEMO ...
Страница 329: ......