![Mitsubishi Electric MELSEC iQ-R CC-Link IE TSN Скачать руководство пользователя страница 291](http://html.mh-extra.com/html/mitsubishi-electric/melsec-iq-r-cc-link-ie-tsn/melsec-iq-r-cc-link-ie-tsn_user-manual_1811879291.webp)
APPX
Appendix 7 Processing Time
289
A
Cyclic transmission delay time
This section describes how to calculate the following cyclic transmission delay times.
• The time between the transmission source CPU module device turning on or off and the transmission destination CPU
module device turning on or off
• The time between data setting in the transmission source CPU module device and the data being stored in the transmission
destination CPU module device
In "Basic Settings" of the master station, when "Communication Period Setting" of the communication destination in "Network
Configuration Settings" is set to an option other than "Basic Period", multiply the LS (communication cycle intervals) by the
multiplier corresponding to the set option, which is specified in "Multiple Period Setting" under "Communication Period
Setting".
At this time, the multiple is as follows, depending on "Communication Period Setting" under "Basic Settings" and "CC-Link IE
TSN Class" under "Network Configuration Settings".
• For "CC-Link IE TSN Class B": The multiple specified in "Multiple Period Setting" in "Communication Period Setting" under
"Basic Settings"
• When "CC-Link IE TSN Class A" and "Communication Period Setting" are "Normal-Speed": The multiple specified in
"Multiple Period Setting" in "Communication Period Setting" under "Basic Settings"
• When "CC-Link IE TSN Class A" and "Communication Period Setting" are "Low-Speed": The multiple
n specified in
"Multiple Period Setting" in "Communication Period Setting" under "Basic Settings"
n can be checked with 'Slave station cyclic transmission information' (Un\G1294304).
Stations with "CC-Link IE TSN Class A" where "Communication Period Setting" is set to "Low-Speed" are grouped by the
sizes of cyclic data sent from the master station to a slave station or cyclic data which the master station receives from a slave
station. The number n is determined by the number of the groups.
Содержание MELSEC iQ-R CC-Link IE TSN
Страница 1: ...MELSEC iQ R CC Link IE TSN User s Manual Application RJ71GN11 T2 ...
Страница 2: ......
Страница 160: ...158 3 PROGRAMMING 3 3 Communication Example of Safety Communication Master station station No 0 ...
Страница 323: ...APPX Appendix 10 Added and Enhanced Functions 321 A MEMO ...
Страница 325: ...I 323 MEMO ...
Страница 329: ......