C1A4H
• There is an error with the command,
subcommand, or request destination
module I/O number specified by the SLMP
message.
• A function that is not supported by the
target device was executed.
• Correct the command, subcommand, or request destination module I/O
number specified by SLMP message.
• Check the version of the target device.
C1A7H
The specified network number is incorrect.
Correct the specified network number.
C1A9H
The specified device number is incorrect.
Correct the specified device number.
C1ADH
The specified data length is incorrect.
Correct the specified data length.
C1CCH
A response with a data length that exceeds
the allowable range was received by the
SLMPSND.
• Execute the instruction again after correcting the request data to be within
the range.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
C200H
The remote password is incorrect.
Correct the remote password, and unlock/lock the remote password again.
C201H
The remote password status of the port used
for communications is in the lock status.
After unlocking the remote password, perform communications.
C202H
When another station was accessed, the
remote password could not be unlocked.
When accessing another station, do not set the remote password on the
relay station or access station, or do not execute the remote password
check on them.
C203H
An error has occurred when checking the
remote password.
Correct the remote password, and unlock/lock the remote password again.
C204H
The device is different from the one
requesting the remote password unlock
processing.
Request the lock processing of the remote password from the external
device that requested the unlock processing of the remote password.
C207H
The file name has too many characters.
Name the file with 255 characters or less.
C208H
The password length is out of range.
Set the password within 6 to 32 characters.
C612H
The module processing was completed with
an error.
• Execute the communication status test, and if the test was completed with
an error, take the corrective action.
• Execute the module communication test, and check that there is no failure
in the module.
C613H
The module processing was completed with
an error.
• Execute the communication status test, and if the test was completed with
an error, take the corrective action.
• Execute the module communication test, and check that there is no failure
in the module.
C615H
The module processing was completed with
an error.
• Execute the communication status test, and if the test was completed with
an error, take the corrective action.
• Execute the module communication test, and check that there is no failure
in the module.
C810H
Remote password authentication has failed
when required.
Set a correct password and perform password authentication again.
C811H
Remote password authentication has failed
when required.
Set a correct password and perform password authentication again one
minute later.
C812H
Remote password authentication has failed
when required.
Set a correct password and perform password authentication again 5
minutes later.
C813H
Remote password authentication has failed
when required.
Set a correct password and perform password authentication again 15
minutes later.
C814H
Remote password authentication has failed
when required.
Set a correct password and perform password authentication again 60
minutes later.
C815H
Remote password authentication has failed
when required.
Set a correct password and perform password authentication again 60
minutes later.
C816H
The security function was activated and
remote password authentication cannot be
performed.
Set a correct password and perform password authentication again after a
certain period of time.
C842H
The routing setting is not set to reach to the
destination network number.
• Execute the link dedicated instruction again after correcting the target
network number/station number.
• When the dynamic routing is used, check that communication path to the
destination network number is set.
• When the dynamic routing is not used, or the module of the series other
than MELSEC iQ-R is included, retry the operation after correcting the
routing setting.
Error
code
Error definition and causes
Action
Detailed
information 1
Detailed
information 2
Содержание MELSEC iQ-R CC-Link IE TSN
Страница 1: ...MELSEC iQ R CC Link IE TSN User s Manual Application RJ71GN11 T2 ...
Страница 2: ......
Страница 160: ...158 3 PROGRAMMING 3 3 Communication Example of Safety Communication Master station station No 0 ...
Страница 323: ...APPX Appendix 10 Added and Enhanced Functions 321 A MEMO ...
Страница 325: ...I 323 MEMO ...
Страница 329: ......