2 PARAMETER SETTINGS
2.5 "CC-Link IE TSN Configuration" Window
125
2
Procedure for clearing a saved parameter
When returning the saved parameters of a not-required slave station to the not-set status, perform the following procedure.
1.
If the saved parameters are to be saved, output them in a CSV file using the [Export] button.
2.
Delete not-required slave stations from the list of stations.
3.
Select the same module as the deleted slave station in "Module List", and drag it to the list of stations or the network
map.
Conditions for clearing a saved parameter
Saved parameters of a slave station can be cleared under the following conditions.
When saved parameters are cleared, execute "Parameter auto-setting" or "Parameter read" in the "Parameter of Slave
Station" window and read the parameters of the slave station.
Item
Description
Target Module Information
Information for the selected slave stations is displayed.
Method selection
Select processing to be executed for selected slave stations.
• Parameter auto-setting: Automatically set contents of "Write Value/Setting Value" to the
slave station. (
Page 91 Slave station parameter automatic setting)
• Parameter read: Read parameters from the selected slave station.
• Parameter write: Write parameters to the selected slave station.
Parameter
Information
[Clear All "Read Value"] button
Click to clear all setting details that were read using "Parameter read".
[Clear All "Write Value/Setting Value"]
button
Click to clear all setting details that are written using "Parameter write".
Processing option
When there are options for processing selected by "Method Selection", setting items are
displayed.
[Import] button
Read contents of parameter processing created in a CSV file.
[Export] button
Output contents of parameter processing set in this window to a CSV file.
Item
Operation
Description
"CC-Link IE TSN
Configuration" window
Open the "CC-Link IE TSN Configuration" window.
When there is not a slave station with the station number that
matches saved parameters in the "CC-Link IE TSN Configuration"
window, saved parameters of the relevant slave station are
skipped.
Skipped parameters of the slave station are cleared.
Reflect setting and close the window.
Saved parameters of a slave station that is not in the actual system
configuration are cleared.
Execute detection of connected/disconnected devices.
All saved parameters are cleared.
Change the function version in the "Properties" window.
When the "Properties" window is closed, saved parameters are
cleared.
"Parameter of Slave
Station" window
Open the "Parameter of Slave Station" window.
Saved parameters that mismatch the relevant slave station are
skipped.
Clicking the [Close with Reflecting the Setting] button in the above
state clears the skipped saved parameters.
Module Parameter
Manually delete "Network Configuration Settings" to apply.
Parameters of "Network Configuration Settings" return to default.
Change the "Setting Method of Basic/Application Settings"
under "Parameter Setting Method" in "Required Settings"
from "Parameter Editor" to "Program".
Change "Station Type" or set parameters that do not exist.
System Parameter
Divert system parameters from another project.
Parameters of the slave station are not diverted.
Module Configuration
Delete a module and check.
Parameters are deleted together with the module.
Navigation window
Delete a module.
Read from PLC
Read module parameters that have a different network
configuration and the same start I/O number.
Parameters are overwritten.
Navigation window
Import the data of a simple motion module to take network
settings.
MELSOFT Navigator
Reflect the parameter.
Saved parameters are cleared.
Содержание MELSEC iQ-R CC-Link IE TSN
Страница 1: ...MELSEC iQ R CC Link IE TSN User s Manual Application RJ71GN11 T2 ...
Страница 2: ......
Страница 160: ...158 3 PROGRAMMING 3 3 Communication Example of Safety Communication Master station station No 0 ...
Страница 323: ...APPX Appendix 10 Added and Enhanced Functions 321 A MEMO ...
Страница 325: ...I 323 MEMO ...
Страница 329: ......