2 PARAMETER SETTINGS
2.3 Basic Settings
107
2
Communication Period Interval (Minimum
value)
The communication cycle intervals that are calculated by the
number of slave stations and the number of points of link devices
by using the values set for standard communications and safety
communications are displayed. Use the displayed value as a
guide.
The displayed value differs depending on "TSN HUB Setting" of
"Connection Device Information" under "Basic Settings" even
when the number of slave stations and link device points are the
same. For details, refer to the following.
Page 293 Communication cycle intervals
The displayed value can be used for "Communication Period
Interval Setting" in "Communication Period Setting" under "Basic
Settings" of the module parameter.
If cyclic transmission is not performed by configuring the setting
with the displayed value, set a value obtained by adding 10% as
follows.
Calculation formula: B+A
0.1
A: Cyclic transmission time (minimum value)
B: Communication cycle interval (minimum value)
When the communication speed of the master station is 1Gbps
in unicast mode or multicast mode with version 1.085P or earlier
of the engineering tool (if a CC-Link IE TSN Class A slave station
with the basic cycle or normal speed cycle exists), the interval
cannot be checked. Check it with 'Communication cycle interval
(calculation value)' (SW0072).
Page 274 List of link special register (SW)
Setting Method
Right-click in the "Safety Communication Setting" window and
select an assignment method in "Safety Data Transfer Device
Setting".
• Start/End: Enter the start and end numbers of safety devices.
• Points/Start: Enter the points and start numbers of safety
devices.
• Start/End
• Points/Start
(Default: Start/End)
No.
Safety connection number for distinguishing settings for each
safety connection.
1 to 120
Communication Destination
Set a network of the communication destination.
Local Network
(Default: empty)
Network
Configuration
Network No.
The network number of the communication destination is
displayed.
Station No.
When the own station is the master station: The station number
of communication destination selected in the "Select the target
module for the Safety Communication Setting" window is
displayed.
IP Address
When the own station is the master station: The IP address of
communication destination selected in the "Select the target
module for the Safety Communication Setting" window is
displayed.
0.0.0.1 to 223.255.255.254
(Default: empty)
Station Type
When the own station is the master station: The station type of
the communication destination selected in the "Select the target
module for the Safety Communication Setting" window is
displayed.
Configured Module
Model Name
When the own station is the master station: The module model
name of the communication destination selected in the "Select
the target module for the Safety Communication Setting" window
is displayed. (Only slave station other than the local station)
Communication
Destination
When the communication destination is a local station: Set the
CPU model name of communication destination.
• R08SFCPU
• R16SFCPU
• R32SFCPU
• R120SFCPU
• R16NCCPU
• CR800-R
(Default: empty)
PLC No.
When the own station is the master station: Set the CPU number
of the communication destination when the CPU module of the
communication destination is set to CPU module other than the
Safety CPU.
2 to 4
(Default: empty)
Item
Description
Setting range
Содержание MELSEC iQ-R CC-Link IE TSN
Страница 1: ...MELSEC iQ R CC Link IE TSN User s Manual Application RJ71GN11 T2 ...
Страница 2: ......
Страница 160: ...158 3 PROGRAMMING 3 3 Communication Example of Safety Communication Master station station No 0 ...
Страница 323: ...APPX Appendix 10 Added and Enhanced Functions 321 A MEMO ...
Страница 325: ...I 323 MEMO ...
Страница 329: ......