1 FUNCTIONS
1.6 CC-Link IE TSN Network Synchronous Communication Function
79
1
Compatible device
The following table shows the devices that can be synchronized by the CC-Link IE TSN network synchronous communication
function.
: Synchronizable,
: Not synchronizable
■
Setting for a station not synchronizable
• When the network synchronous communication setting is set for a slave station that is not synchronizable, Initialization
failure (parameter mismatch between master and slave stations) (event code: 00C71) is displayed in the event history in
the master station. (Network synchronous communication and cyclic transmission with other slave stations are continued.)
• In the local station for which "Network Synchronous Communication" in "Network Configuration Settings" under "Basic
Settings" of the master station is set to "Synchronous", if "Select Inter-module Synchronization Target Module" in "System
Parameter" on the local station side is set to "Asynchronous", Inter-module synchronization target mismatch (error code:
3601H) occurs.
Support of the CC-Link IE
TSN Network
synchronous
communication function
CC-Link IE TSN Class
Communication speed
Communication cycle
setting
Synchronizability
Not supported
Supported
CC-Link IE TSN Class A
device
CC-Link IE TSN Class B
device
1Gbps
Basic Period
Normal-Speed
Low-Speed
100Mbps
Basic Period
Normal-Speed
Low-Speed
Содержание MELSEC iQ-R CC-Link IE TSN
Страница 1: ...MELSEC iQ R CC Link IE TSN User s Manual Application RJ71GN11 T2 ...
Страница 2: ......
Страница 160: ...158 3 PROGRAMMING 3 3 Communication Example of Safety Communication Master station station No 0 ...
Страница 323: ...APPX Appendix 10 Added and Enhanced Functions 321 A MEMO ...
Страница 325: ...I 323 MEMO ...
Страница 329: ......