A
SW0110 to
SW0117
CPU minor error
status of each
station
Stores the minor error occurrence status of each station.
When the target station is the RJ71GN11-T2, the occurrence status on the CPU
module is stored.
0: Normal, or a moderate or serious error occurring
1: Minor error occurring
Each number in the table represents a station number.
is fixed to 0.
(Conditions)
• Reserved stations and stations that surpass the maximum station number are
ignored.
• Since a local station cannot obtain the station information of the CC-Link IE
TSN Class A remote station when communicating in multicast mode, "0:
Normal, or a moderate or serious error occurring" is reflected to the CC-Link IE
TSN Class A remote station.
SW0160 to
SW0167
Execution result
of slave station
parameter
automatic setting
function
When the slave station parameter automatic setting is completed with an error,
the bit of the target station is turned on.
Off: Completed successfully
On: Completed with an error
When completed with an error, the error code is stored in the SW0194.
When completed with an error caused by the master station, the bit is not turned
on.
Each number in the table represents a station number.
is fixed to 0.
SW0194
Detailed
execution result
of slave station
parameter
automatic setting
When the slave station parameter automatic setting is completed with an error,
the error code is stored.
When completed with an error caused by the slave station, the bit of the target
station of 'Execution result of slave station parameter automatic setting function'
(SW0160 to SW0167) is turned on.
SW0198
Link dedicated
instructions
processing result
CH3
Stores the processing results of the link dedicated instruction that used channel 3
of the own station.
0: Completed successfully
1 or greater: Completed with an error (Error code is stored.)
SW0199
Link dedicated
instructions
processing result
CH4
Stores the processing results of the link dedicated instruction that used channel 4
of the own station.
0: Completed successfully
1 or greater: Completed with an error (Error code is stored.)
SW019A
Link dedicated
instructions
processing result
CH5
Stores the processing results of the link dedicated instruction that used channel 5
of the own station.
0: Completed successfully
1 or greater: Completed with an error (Error code is stored.)
No.
Name
Description
Availability
Master
station
Local station
Unicast
mode
Multicast
mode
16 15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
120 119 118 117 116 115 114 113
SW0111
SW0112
SW0113
SW0114
SW0115
SW0116
SW0117
SW0110
16 15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
120 119 118 117 116 115 114 113
SW0161
SW0162
SW0163
SW0164
SW0165
SW0166
SW0167
SW0160
Содержание MELSEC iQ-R CC-Link IE TSN
Страница 1: ...MELSEC iQ R CC Link IE TSN User s Manual Application RJ71GN11 T2 ...
Страница 2: ......
Страница 160: ...158 3 PROGRAMMING 3 3 Communication Example of Safety Communication Master station station No 0 ...
Страница 323: ...APPX Appendix 10 Added and Enhanced Functions 321 A MEMO ...
Страница 325: ...I 323 MEMO ...
Страница 329: ......