1 FUNCTIONS
1.5 RAS
71
1
Program that detects loopback station numbers (master operating station only)
By detecting loopback station numbers, a faulty station can be found. Whether loopback is being performed or not can be
checked using 'Network topology setting' (SB0078) and 'Loopback status' (SB0065) of the master operating station.
Ex.
Program that stores loopback station numbers to 'wLoopbackStationNumber_1' (D1000) and 'wLoopbackStationNumber_2'
(D1001)
Precautions
■
Supported version
To use the loopback function, check that all stations support ring topology. (
Page 320 Added and Enhanced Functions)
■
Loopback function setting and network configuration
To use the loopback function, configure the network in ring topology and set "Network Topology" to "Ring" in "Basic Settings"
of the master station. If "Network Topology" and the network configuration are inconsistent, an error may occur in all stations
and data link cannot be performed.
■
When a loopback occurs or a loopback is resolved
Due to the occurrence or resolution of a loopback, transient transmission may become temporarily impossible. The following
shows the periods of time until transient transmission becomes possible again.
• A period of time until transient transmission becomes possible after the occurrence of a loopback: Maximum 1.1 seconds
• A period of time until transient transmission becomes possible after the resolution of a loopback: Maximum 1.3 seconds
Transient transmission executed at the time of the occurrence or resolution of a loopback may be completed with an error. In
such a case, execute transient transmission again. For a dedicated instruction, set transient transmission so that it will not be
completed with an error by increasing the number of resends or extending the monitoring time.
Classification
Label name
Description
Device
Module label
GN11_1.bSts_DataLinkError
Data link error status of own station
SB0049
GN11_1.bOpe_Loopback
Loopback status
SB0065
GN11_1.bSet_RingTopology
Network topology setting
SB0078
GN11_1.wnVal_LoopbackStationNumber[1]
Loopback station number 1
SW0070
GN11_1.wnVal_LoopbackStationNumber[2]
Loopback station number 2
SW0071
Label to be defined
Define global labels as shown below:
(3) When 'Network topology setting' (SB0078) and 'Loopback status' (SB0065) are on, 'Loopback station number 1' (SW0070) and 'Loopback station number 2'
(SW0071) are saved.
Содержание MELSEC iQ-R CC-Link IE TSN
Страница 1: ...MELSEC iQ R CC Link IE TSN User s Manual Application RJ71GN11 T2 ...
Страница 2: ......
Страница 160: ...158 3 PROGRAMMING 3 3 Communication Example of Safety Communication Master station station No 0 ...
Страница 323: ...APPX Appendix 10 Added and Enhanced Functions 321 A MEMO ...
Страница 325: ...I 323 MEMO ...
Страница 329: ......