5.6.2 External Fault Response Selection
It is sometimes desirable to have at least one external fault input to the VFD. To properly program a multi-function
input (H01.01 to H01.07) for this purpose an external fault response must be selected. The table below shows the
possible selections for an external fault response.
Table 5-6: External Fault Response Selection
(1) N.O. = normally open contact; N.C. = normally closed contact
(2) Uses B05.08 timer
External Fault Selection
Input Level Selection
Detection Method
External Fault Action
MFDI Setting
N.O.
(1)
N.C.
(1)
Always
During
Run
Ramp to
Stop
Coast to
Stop
Fast-stop
(2)
Alarm
Only
√
√
√
20
√
√
√
24
√
√
√
28
√
√
√
2C
√
√
√
22
√
√
√
26
√
√
√
2A
√
√
√
2E
√
√
√
21
√
√
√
25
√
√
√
29
√
√
√
2D
√
√
√
23
√
√
√
27
√
√
√
2B
√
√
√
2F