IMPULSE
®
•G+ Mini Technical Manual
November 2020
Page 107
Figure 5-27: Motor Protection Operation Time
L01.03
Motor Overheat Alarm
Selection
Operation when the motor temperature analog
input exceeds the OH3 alarm level. (1.17V)
(H03.02 or 10 = 0E)
00–04
03
00 Decel to Stop
01 Coast to Stop
02 Fast Stop by B05.08
03 Alarm Only (OH3 Flashes)
04 Stop by B03.03 Method
L01.04
Motor Overheat Fault Selection Operation when the motor temperature analog
input exceeds the OH4 fault level. (2.34V) (H03.02
or 10 = 0E)
00–03
03
00 Decel to Stop
01 Coast to Stop
02 Fast Stop by B05.08
03 Stop by B03.03 method
L01.05
Motor Temp Filter
Motor temperature analog input filter time constant
0.00–
10.00sec
0.20
L01.13
Overload Operation Selection
Determines whether or not to hold the
Electrothermal value when power is interrupted
00–01
01
00 Disable
01 Enable
Parameter Name
Function
Range
Default
Содержание IMPULSE G+ Mini
Страница 15: ...IMPULSE G Mini Technical Manual November 2020 Page 15 Figure 2 1 Long Time Storage...
Страница 17: ...IMPULSE G Mini Technical Manual November 2020 Page 17 Figure 2 2 Diagram A Figure 2 3 Diagram B...
Страница 18: ...IMPULSE G Mini Technical Manual November 2020 Page 18 Figure 2 4 Diagram C...
Страница 56: ...IMPULSE G Mini Technical Manual November 2020 Page 56 Figure 5 8 DC Injection Brake Time Calculation...
Страница 181: ......
Страница 182: ...IMPULSE G Mini Adjustable Frequency Crane Controls Technical Manual November 2020...