Chapter 7 Detailed Explanations of Functional Parameters
If P414 is too high, DC voltage may be too high and may cause
inverter protection.
If P414 is too low, braking resistor maybe too hot.
P415 Braking duty
This parameter decides the working duty of the braking resistor.
Higher duty needs high power of braking resistor.
P416
Restart after instant power off Default value 0
Range
0-1
Unit
1
Settings
0: Invalid: no restart after instant power failure
1: Valid: frequency tracing start-up
0: Invalid
Inverter clears the running command after power failure. After power
is recovered, inverter will not start automatically.
1: Frequency tracing enable
When power is shut-off in short time, inverter keeps the running
command as effective. When power is recovered in time, inverter
will tracing the motor speed and resume output.
Attention: when instant power failure restarting is enabled, inverter
may start the motor automatically. Please take care of the safety
when use this function.