64
·
Operation Instruction of S900 E Series Inverter
·
65
·
still operate at this value.
The value of P300 and that of P301 decide the range of input
voltage.
P302 Input filter time
Value of input filter time decides the response speed of inverter to
analogue change. With the increase of value of P302, the inverter
will get slower for responding to analogue change.
P303
FIC minimum current input Initial value: 0
Setting range
0~FIC maximum current
input
Unit
0.1
P304
FIC maximum current input Initial value: 20.0
Setting range
FIC minimum current
input-20.0
Unit
0.1
P305
FIC input filter time Initial value: 1.0
Setting range
0-25.0
Unit
0.1
P303: FIC minimum current input
FIC minimum current input is related to frequency of lowest
analogue input. Inverter will deem current signal below value of
P303 as invalid.
P304: FIC maximum current input
FIC maximum current input is related to frequency of highest
analogue input. For current command higher than value of P304,
inverter will operate at the value.
P305: FIC input filter time
FIC input filter time decides how fast inverter responds to analogue
change. With the increase of value of P305, inverter will respond
more and more slowly to analogue change. The output of inverter
will be relatively stable.
Refer to explanations of P300 to P302 for relevant parameters.
If the external input is voltage signal, refer to P300-P302. If the