30
·
Operation Instruction of S900 E Series Inverter
·
31
·
Function
Parameters
Name
Setting Range
Minimum
Setting
increments
Initial value
Refer
To
Page
Basic functions
P200 Start mode
selection
0: regular start
1: restart after
inspection
1
0
57
P201 Stop mode
selection
0: deceleration to a
stop
1: coasting
1
0
58
P202 Starting
frequency
0.10~10.00Hz
0.01
0.5
58
P203 Stopping
frequency
0.10~10.00Hz
0.01
0.5
59
P204
DC injection
brake
operation
current (start)
0~150% rated motor
current
1%
100%
59
P205
DC injection
brake
operation time
(start)
0~25.0S
0.1
0
59
P206
DC injection
brake
operation
current (stop)
0~150% rated motor
current
1%
100%
60
P207
DC injection
brake
operation time
(stop)
0~25.0S
0.1
0
60
P208 Torque boost
0~20.0%
1
5%
60
P209 Rated motor
voltage
0~500.0V
0.1
380.0
61
P210 Rated motor
current
0~current of system
0.1
Changing 61
P211
No load current
ratio of motor
0~100%
0.1
40%
61
P212 Rated motor
rotation speed 0~6000r/min
1
1420
61
P213
Number of
motor poles
0~20
1
4
61