28
·
Operation Instruction of S900 E Series Inverter
·
29
·
Function
Parameters
Name
Setting Range
Minimum
Setting
increments
Initial value
Refer
To
Page
Monitor functions
P014
The frequency
setting in the
last alarm.
Read only
-----
-----
44
P015
The output
frequency in
last alarm.
Read only
-----
-----
44
P016
The output
current in last
alarm.
Read only
-----
-----
44
P017
The output
voltage in last
alarm.
Read only
-----
-----
44
P018
The output DC
bus voltage in
last alarm.
Read only
-----
-----
44
Basic functions
P100
Digital
frequency
setting
0.00—Maximum
frequency
0.01
0.00
46
P101
Frequency
setting
selection
0: Digital frequency
setting (P100)
1: Analog voltage
(0—10VDC)
2: Analog current
(0—20mADC )
3. Setting dial
(Operation panel)
4 UP/DOWN
frequency setting
5: RS485
communication
frequency setting
1
0
46
P102 Start signal
selection
0: Operation panel
(FWD/REV/STOP)
1: I/O terminal
2: Communication
(RS485)
1
0
49
P103
“stop” key
lock operation
selection
0: “Stop”key lock
mode invalid
1: “Stop” key lock
mode valid
1
1
51