Chapter 7 Detailed Explanations of Functional Parameters
When winding function is complete, this contact is ON. When
inverter stops, this contact is reset.
27: Set counter reached
When inverter implements external counter, and when count value
arrives at setting value (P425), this contact is ON.
28: Middle counter reached
When inverter counts, if count value arrives at setting value (P426),
this contact is ON.
P326
Output terminal FOV Default value 0
Setting range 0-7
Unit
1
P327
Output terminal FOC Default value 1
Setting
0: Output frequency
1: Output current
2: Direct voltage
3: Alternating voltage
P326 output terminal FOV
FOV terminal may output 0-10V voltage, output may be setting in
range of 0-10V through P306 and P307 and being corresponding to
output frequency, output current, direct voltage, alternating voltage
and so on.
P327 output terminal FOC
FOC terminal may output 0-20m current, output range may be
setting by P308 and P309 and being corresponding to output
frequency, output current, direct voltage, alternating voltage and so
on.
0: Output frequency:
Current (voltage) output is corresponding to Min. output
frequency~max. frequency.
1: Output current
Current (voltage) output is corresponding to 0~2 × inverter rated
current.