Operation Instruction of S900 E Series Inverter
·
99
·
2: PID starts up on condition; PID will start when certain external
input is ON.
P601
PID operation mode selection Initial value: 0
Setting range 0-1
Unit
1
Content:
0: Negative feedback mode
1: Positive feedback mode
0: Negative feedback mode
If feedback value(P603)>setting value(P602), inverter decrease
output frequency
If feedback value(P603)<setting value(P602), inverter increase
output frequency
1: Positive feedback mode
If feedback value(P603)>setting value(P602), inverter decrease
output frequency
If feedback value(P603)<setting value(P602), inverter increase
output frequency
P602
PID action set point Initial value:0
Setting range
0-2
Unit
1
Content:
0: figure mode (P604)
1: FIV
2: FIC
0: Select figure mode as the set point (P604)
Set the set value (P604) from the operation panel or parameter unit.
1: FIV
Terminal FIV input is the set point (0—10DCV).
2: FIC.
Terminal FIC input is the set point (0—20mA).
P603
PID feedback value selection Initial value: 0
Setting range
0-3
Unit
1
Content:
0: FIV 1: FIC 2: FIV-FIC