78
·
Operation Instruction of S900 E Series Inverter
·
79
·
10: Timer 1 reached
11: Timer 2 reached
When inverter arrives at setting value, this contact is ON, when
timer start-up signal is removed, this contact is reset.
12: Stage completion indication
In the PLC operation mode, inverter output this pulse signal when
inverter finished a section of program.
Running command
Stage completion indicating
Process commpletion
indicating
Program setting: stop after
three cycles of operation
13. Process completion indication
In the PLC operation mode, inverter output this pulse signal when
inverter finished the entire program.
14. PID upper limit
When PID feedback quantity exceeds setting value of upper limit,
this contact is ON.
15: PID lower limit
When PID feedback quantity is lower than setting value, this contact
is ON.
16: 4-20mA cable open
When FIC input signal is disconnected, this contact is ON and
alarms.
17: Overload detection
When inverter detects that motor overloads, this contact is ON.
18: Over torque detection
When inverter detects over torque, this contact is ON.
26: Winding function complete