Operation Instruction of S900 E Series Inverter
·
59
·
High current is likely in start, it is also possible to cause current.
Therefore, you need to have over current level setup (4.09 setup).
The specific value depends on the load.
In addition, when the value of 4.09 is too low, it may lead to a long
start time. If over current in the speed tracing, inverter will pause the
speed tracing.
P201
Stop mode selection Initial value : 0
Setting range
0-1
Unit
1
Explanation
0: Deceleration to stop
1: Coasting stop
You can choose a suitable stop mode according to the actual load.
0: Deceleration to stop
Once inverter receives stop command, it will reduce the output
frequency according to the deceleration time.
Running
frequency
Shutdown
frequency
Shutdown duration
DC braking
Free running shutdown
F
With regard to stop mode after stop frequency is reached, you can
choose DC injection brake and other options. If you do not choose
DC injection braking, it will stop in coasting stop mode.
1: Coasting stop
When inverter receives stop command, it will stop frequency output
and it will have free running with load until it stops.
P202
Start frequency setting Initial value : 0.5
Setting range
0.10-10.00
Unit
0.01