Chapter 7 Detailed Explanations of Functional Parameters
Example: PID action set point is 60% (0 – 100% is corresponding
to 0 – 10V), and the wake-up value is 80%, which is actually
corresponding to 0 – 10V, then the actual wake-up value is 60% ×
80% = 48% (corresponding to 0 – 10V).
P614
PID corresponding value of display Initial value : 1000
Setting range
0 – 1000
Unit
1
P615
PID digit of display Initial value : 4
Setting range
0 – 5
Unit
1
0: Not display PID feedback value 3: Display 3 digits
1: Display 1 digit 4: Display 4 digits
2: Display 2 digits 5: Display 5 digits
P616
PID decimal digit of display Initial value : 1
Setting range
0 – 4
Unit
1
Content:
0: Not display after decimal point
1: Display 1 digit after decimal point
2: Display 2 digits after decimal point
3: Display 3 digits after decimal point
4: Display 4 digits after decimal point
P614 PID corresponding value of display.
P614 setting value is corresponding to + 10V analog voltage.
If P614 is set as 200, then it indicates that full span is 200,
corresponding to + 10V voltage.
P615 sets the digit display.
0 indicates not displaying feedback value. Users may select the digit
displayed according to actual need.
P616 PID decimal digit of display.
P616 sets the digit displayed after decimal point.
For example: Four-digit display is required, with 1 digit displayed after
decimal point, target value is set as 50%, and PID corresponding
value of display is 200.
Then, the display value is 200 × 50% = 100.0 and the parameter