Operation Instruction of S900 E Series Inverter
·
109
·
ASCII mode:
RTU mode:
Format of enquiry message:
Address
01H
Function
03H
Starting data
address
21H
02H
Number of data
(count by word)
00H
02H
CRC CHK Low
6FH
CRC CHK High
F7H
Format of response message:
Address
01H
Function
03H
Number of data
(count by byte)
04H
Content of data
address 8102H
17H
70H
Content of data
address 8103H
00H
00H
CRC CHK Low
FEH
CRC CHK High
5CH
STX
‘:’
Address
‘1’
‘0’
Function
‘0’
‘3’
Starting address
‘2’
‘1’
‘0’
‘2’
Number of data
(count by word)
‘0’
‘0’
‘0’
‘2’
LRC Check
‘D’
‘7’
END
CR
LF
Format of enquiry message
character string:
Format of response message
character string:
STX
‘:’
Address
‘0’
‘1’
Function
‘0’
‘3’
Number of data
(count by byte)
‘0’
‘4’
Content of starting
address 2102H
‘1’
‘7’
‘7’
‘0’
Content of address
2103 H
‘0’
‘0’
‘0’
‘0’
LRC Check
‘7’
‘1’
END
CR
LF