82
·
Operation Instruction of S900 E Series Inverter
·
83
·
P409
Accelerating torque
limitation level
Output frequency
Current
100% current is the rated current of inverter, when P409 is set to
be 0, then accelerating torque limit is invalid, and it does not have
protecting function.
P410
Constant-speed torque limiting level Default value 00
Range
0-200
Unit
1
Parameter P409 is the torque limit level during constant speed. When
output current reaches the setting value, inverter automatically
reduce the output frequency in order to reduce the load. When
the output current drops, inverter increase output frequency to the
setting (100% current is rated current of inverter).
When P410 is set to be 0, constant-speed torque limiting level is
invalid and cannot protect.
Current
Output frequency
P410
P411
Deceleration over-voltage prevention selection Default value 1
Range
0-1
Unit
Settings
0:Invalid 1:Valid