Operation Instruction of S900 E Series Inverter
·
81
·
2: Direct voltage
Current (voltage) output is corresponding to 0~1000V.
3: Alternating voltage
Current (voltage) output is corresponding to 0~510V.
For example: select a frequency meter of 0~5V, supervise output
frequency, setting the Min. output frequency of inverter as 0.00Hz,
the highest output frequency is 80Hz.
Then:
Modor
M
R
S
T
U
V
W
FWD
GND
S900 E
FOV
GND
E
V
F
80Hz
0
5V
V
Parameter: P105=80.00 Max. frequency
P106=0.00 Min. output frequency
P306=0.00 FOV minimum voltage output
P307=5.00 FOV maximum voltage output
7-5 Secondary application group
P400
Jog frequency setting Default value 5.00
Range
0.00---max. frequency
Unit
0.01
Jog frequency setting is usually applied to trial run. This function
can only be through external terminal.
When JOG function is achieved, other instruction is invalid. When
JOG signal is open, inverter decelerate to stop, JOG acceleration/
deceleration time is set in the 4th acceleration/ deceleration
parameter.
Control priority level: